Data just before the latest failure
Contents of Check 2
Press “” to go to the next page. Press “” to go to the previous page.
Continue from previous page
Temperature Status Display
1 Inlet Air Temperature q1 23 Corresponds to item “b2” in Check 1.
2 Outlet Air Temperature q2 50 Corresponds to item “b3” in Check 1.
3
IDU Heat Exchanger Liquid Piping
(frozen) Temperature
q3 25 Corresponds to item “b4” in Check 1.
4 Outdoor Temperature q4 12 Corresponds to item “b6” in Check 1.
5 Gas Pipe Temp. q5 25 Corresponds to item “b7” in Check 1.
6 Evaporating Temp. at Heating q6 03 Corresponds to item “b8” in Check 1.
7 Control Information q7 -- Corresponds to item “b9” in Check 1.
8 Compressor temperature q8 45 Corresponds to item “bA” in Check 1.
Pressure / Frequency
9 Discharge Pressure q9 18 Corresponds to item “H1” in Check 1. Unit is (×0.1MPa).
10 Inlet Pressure qA 04 Corresponds to item “H2” in Check 1. Unit is (×0.1MPa).
11 Control Information qb 44 Corresponds to item “H3” in Check 1.
12 Operating Frequency (Hz) qC 44 Corresponds to item “H4” in Check 1.
Electronic Expansion Valve
13 IDU Electronic Expansion Valve (%) qd 20
Corresponds to item “L1” in Check 1.
14 ODU Electronic Expansion Valve1 (%) qE 99
Corresponds to item “L2” in Check 1.
Current Value (reference)
15 Compressor Current (A) qF 20
Corresponds to item “P1” in Check 1.
SERVICE & INSTALLATION MENU