Instruction Manual
Table Of Contents
- 1 Safety summary
- 2 Switch Names and Functions
- 3 Operation
- 4 Icon Description
- 5 Function Menu
- 5.1 Simple Timer Setting
- 5.2 Operation Schedule Setting
- 5.3 Power Savings Setting
- 5.4 Night Quiet Operation
- 5.5 Power Saving/Night Quiet Schedule Setting
- 5.6 Power Consumption Display
- 5.7 Autoboost (QUICK MODE) Setting
- 5.8 Comfort Setting
- 5.9 Motion sensor setting
- 5.10 Setback Setting
- 5.11 Elevating Grille
- 5.12 Filter Reminder Reset Setting
- 5.13 FrostWash
- 5.14 Individual Louver Setting
- 5.15 Cancel Individual Louver Setting
- 5.16 Louver Open/Close
- 5.17 Ventilation
- 5.18 Total Heat Exchanger Setting
- 6 Service & installation menu
- 6.1 Installation menu
- 6.1.1 Test Run
- 6.1.2 Function selection
- 6.1.3 Thermistor Selection
- 6.1.4 Input / Output Setting
- 6.1.5 Thermistor Calibration in Controller
- 6.1.6 Fan Speed at Cooling Thermo-OFF
- 6.1.7 Fan Speed at Heating Thermo-OFF
- 6.1.8 Indoor Unit Address Change
- 6.1.9 Address Check Operation
- 6.1.10 Address Initialization
- 6.1.11 Setting Initialization
- 6.1.12 Main Remote Setting
- 6.1.13 Priority Setting
- 6.1.14 Cancel Preheating Control
- 6.1.15 Elevating grille Setting
- 6.1.16 Power Up Setting
- 6.1.17 Setback Trigger Unit
- 6.1.18 Refrigerant Leak Sensor Setting
- 6.2 Service menu
- 6.3 Check Menu
- 6.1 Installation menu
- 7 Screen Display Setting menu
- 8 Contact Information menu
- 9 Hotel Mode Setting
- 10 In Alarm Condition
Data just before the latest failure
Contents of Check 2
Press “∨” to go to the next page. Press “∧” to go to the previous page.
Continue from previous page
➪
Temperature Status Display
1 Inlet Air Temperature q1 23 Corresponds to item “b2” in Check 1.
➪
2 Outlet Air Temperature q2 50 Corresponds to item “b3” in Check 1.
➪
3
IDU Heat Exchanger Liquid Piping
(frozen) Temperature
q3 25 Corresponds to item “b4” in Check 1.
➪
4 Outdoor Temperature q4 12 Corresponds to item “b6” in Check 1.
➪
5 Gas Pipe Temp. q5 25 Corresponds to item “b7” in Check 1.
➪
6 Evaporating Temp. at Heating q6 03 Corresponds to item “b8” in Check 1.
➪
7 Control Information q7 -- Corresponds to item “b9” in Check 1.
➪
8 Compressor temperature q8 45 Corresponds to item “bA” in Check 1.
➪
Pressure / Frequency
➪
9 Discharge Pressure q9 18 Corresponds to item “H1” in Check 1. Unit is (×0.1MPa).
➪
10 Inlet Pressure qA 04 Corresponds to item “H2” in Check 1. Unit is (×0.1MPa).
➪
11 Control Information qb 44 Corresponds to item “H3” in Check 1.
➪
12 Operating Frequency (Hz) qC 44 Corresponds to item “H4” in Check 1.
➪
Electronic Expansion Valve
13 IDU Electronic Expansion Valve (%) qd 20
Corresponds to item “L1” in Check 1.
➪
14 ODU Electronic Expansion Valve1 (%) qE 99
Corresponds to item “L2” in Check 1.
➪
Current Value (reference)
15 Compressor Current (A) qF 20
Corresponds to item “P1” in Check 1.
SERVICE & INSTALLATION MENU
PMML0565 rev.1 - 04/202286