2.5.4 Signal contact
Only device variants featuring supply voltage with characteristic value C
(24 V DC ... 48 V DC), K (60 V DC ... 250 V DC / 110 V AC ... 230 V AC,
50 Hz ... 60 Hz) or W (24 V DC) have a signal contact.
For the signal contacts to be connected, make sure that the following
requirements are met:
The electrical wires are voltage-free.
The connected voltage is limited by a current limitation device or a fuse.
Observe the electrical threshold values for the signal contact.
See “General technical data” on page 63.
Connect the signal contact lines according to the pin assignment with a
suitable socket.
Plug the socket into the M12 plug on the device.
The tightening torque of the locking screw is 5.3 lb-in (0.6 Nm).
2.6 Operating the device
By connecting the supply voltage via a 7/8" plug or a twisted pair cable
(Power over Ethernet), you start the operation of the device.
Pin Function
1 Signal contact 2
2 Signal contact 2
3 Signal contact 1
4 Signal contact 1
Table 12: Pin assignment of the signal contact, 4-pin, “A”-coded M12 plug
WARNING
ELECTRIC SHOCK
Before connecting the electrical wires, always verify that the requirements
listed are complied with.
See “Requirements for connecting electrical wires” on page 10.
See “Requirements for connecting the supply voltage” on page 10.
Failure to follow this instruction can result in death, serious injury, or
equipment damage.