User's Manual

Table Of Contents
Installation BAT-F
Release
18
07/2020
15
Rev.: 0
page 2 of 2
For Use in Hazardous Locations Class I, Division 2 Groups A, B, C, D:
Only allowed for BAT-F model No’s. which are individually labelled
“FOR USE IN HAZARDOUS LOCATIONS”
Non-incendive field wiring circuits must be wired in accordance with the
National Electrical Code (NEC), NFPA 70 , article 501.
WARNING – EXPLOSION HAZARD – SUBSTITUTION OF ANY
COMPONENTS MAY IMPAIR SUITABILITY FOR HAZARDOUS
LOCATIONS OR EXPLOSIVE ATMOSPHERES.
WARNING – EXPLOSION HAZARD – DO NOT DISCONNECT
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF
OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.
Notes:
The non-incendive field wiring circuit concept allows interconnection of
non-incendive field wiring apparatus and associated nonincendive field wiring
apparatus using any of the wiring methods permitted for unclassified locations
when certain parametric conditions are met.
Capacity: C
a
or C
0
C
i
+ C
Cable
;
Inductivity: L
a
or L
0
L
i
+ L
Cable
CONTROL DRAWING for BAT-F devices according to
Class 1, Division 2 Hazardous Locations or according to the
European Directive 2014/34/EU
Document No.: 000183360DNR