Installation BAT-F
Release
18
07/2020
CONTROL DRAWING for BAT-F devices according to
Class 1, Division 2 Hazardous Locations or according to the
European Directive 2014/34/EU
Rev.: 0 Document No.: 000183360DNR
Ordinary Location,
Non-Hazardous Area,
Non-Explosive Atmosphere
Zone 2
Explosive Atmosphere
Class 1, Division 2
Groups A, B, C, D
Hazardous Location
or
Relay contacts. Equipment with
non-incendive field wiring parameters.
Polarity is not relevant.
THE RELAY TERMINALS ARE
DEPENDENT UPON THE FOLLOWING
ENTITY PARAMETERS:
V
max
or l
max
or I
i
C
i
L
i
30 V 90 mA 2 nF 1 μH
Supply voltage with characteristic value W:
16.8 V DC – 32 V DC;
Ambient Temperature rating:
Ta: 0 °C to +60 °C for temperature range with
characteristic value “S”
Temperature Code: T4
i
U
Supply voltage with characteristic value C:
18 V DC – 60 V DC;
Supply voltage with characteristic value K:
88 V AC – 265 V AC or
48 V DC – 320 V DC
Ta: 40 °C to +70 °C for temperature range
with characteristic value “T” or “E”
(The characteristic value is part of the
type designation on the device.)
Relais
P2
P1
The earth conductor must be at least the
same wire size (mm
2
oder AWG) as the
supply conductors.
BAT-F WLAN-Access-
Point/-Client
page 1 of 2