User's Manual
Table Of Contents
- Installation
- Contents
- Safety instructions
- General safety instructions
- Certified usage
- Installation site requirements
- Device casing
- Qualification requirements for personnel
- National and international safety regulations
- Grounding the device
- Lightning protection
- Requirements for connecting electrical wires
- Requirements for connecting the supply voltage
- ATEX directive 2014/34/EU – specific regulations for safe operation
- Relevant for use in explosion hazard areas (Hazardous Locations, Class I, Division 2):
- E marking
- CE marking
- LED or laser components
- FCC note
- Note for the use in the Japan
- Note for the use in Oman
- Recycling note
- About this manual
- Key
- 1 Description
- 1.1 General description
- 1.2 Device name and product code
- 1.3 Device view
- 1.4 Power supply
- 1.4.1 Supply voltage with the characteristic value C (24 V DC ... 48 V DC)
- 1.4.2 Supply voltage with the characteristic value K (60 V DC ... 250 V DC / 110 V AC ... 230 V AC, 50 Hz ... 60 Hz)
- 1.4.3 Supply voltage with the characteristic value P (Power supply only through PoE)
- 1.4.4 Supply voltage with the characteristic value W (24 V DC)
- 1.5 Ethernet ports
- 1.6 Connections for antennas
- 1.7 Display elements
- 1.8 Management interfaces
- 1.9 Signal contact
- 1.10 Reset button
- 2 Installation
- 3 Making basic settings
- 4 First login (Password change)
- 5 Obtain compliance for operation in the European Union
- 6 Configuring the transmit power
- 7 Configuring the transmit power for the 4.9 GHz band
- 8 Maintenance and service
- 9 Disassembly
- 10 Technical data
- 10.1 General technical data
- 10.2 Dimension drawings
- 10.3 Radio technology
- 10.4 Roaming
- 10.5 Receiving sensitivity, transmit power, and data rate of the WLAN module version EWLAN1 (Approvals 2, characteristic value M or 9)
- 10.6 Receiving sensitivity, transmit power, and data rate of the WLAN module version EWLAN1 for device variants with approval for the 4.9 GHz band (Approvals 2, characteristic value P)
- 10.7 Receiving sensitivity, transmit power, and data rate of the WLAN module version EWLAN2 for high-gain antennas (Approvals 2, characteristic value H)
- 10.8 EMC and immunity
- 10.9 Network range
- 10.10 Power consumption/power output
- 11 Scope of delivery, order numbers and accessories
- 12 Underlying technical standards
- A Further support
12
Installation BAT-F
Release
18
07/2020
ATEX directive 2014/34/EU – specific regulations for safe
operation
In Ex zone 2, only devices with a corresponding label may be operated.
When operating the BAT-F types with characteristic value G for
Approvals 1 (ATEX zone 2), the following applies:
Never use the supply voltage with characteristic value K (60 V DC ...
250 V DC / 110 V AC ... 230 V AC, 50 Hz ... 60 Hz) in Ex zone 2.
II 3 G Ex nA IIC T4 Gc DEKRA 13ATEX0153 X
40 °F ... +158 °F (40 °C ... +70 °C) for temperature range
characteristic value T and E
+32 °F ... +140 °F (0 °C ... +60 °C) for temperature range
characteristic value S
DO NOT OPEN THE DEVICE WHEN IT IS ELECTRICALLY CHARGED.
THE USB CONNECTOR MUST NOT BE USED WHEN THE DEVICE IS
OPERATED IN EXPLOSIVE HAZARDOUS LOCATIONS.
Special conditions for safe use
For supply voltage with characteristic value C (24 V DC ... 48 V DC)
and W (24 V DC):
Provisions shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 119 V.
When the temperature under rated conditions exceeds 158 °F (70 °C)
at the cable or conduit entry point, or 176 °F (80 °C) at the branching
point of the conductors, take care that the temperature specification of
the selected cable is in compliance with the actual measured
temperature values.
Install the modules in a suitable enclosure in accordance with
EN 60079-15 providing a degree of protection of at least IP54
according to EN 60529, taking into account the environmental
conditions under which the equipment will be used.
Relevant for use in explosion hazard areas (Hazardous
Locations, Class I, Division 2):
In Ex zone 2, only the devices with a corresponding label may be
operated in explosion hazard areas Class I, Division 2.
Temperature code T4 Ambient temperature 40 °F ... +158 °F (40 °C ... +70 °C ;
temperature range with characteristic value T and E)
Ambient temperature +32 °F ... +140 °F (0 °C ... +60 °C;
temperature range with characteristic value S)
List of standards EN 60079-0:2012 + A11
EN 60079-15:2010