User guide

Part No. 4801-5338 Rev 01-10 Evolution 4000 19 of 86
Refer to Section 6.4.2 & 7.9.
When Mode=Off, those stages will not
be visible on the Stage Conditions
Screen.
STAGE CONDITIONS SCREEN EXAMPLE:
Refer to Section 7.13.
Refer to Section 6.4.3, 7.6, & 7.11.7.
Target: The desired temp. of the building.
Enter Tun: Fans enter Tunnel at set temp.
Exit Tun: Fans exit Tunnel at set temp.
N/A: The stage is not allowed to turn on with the current set conditions.
Off: The stage is currently OFF.
On: The stage is currently ON.
Timed: The stage is currently ON with a timer.
Refer to Section 7.12.
Refer to Section 6.4.1 & 7.5.
Refer to Section 6.4.1 & 7.5.
Refer to Section 6.4.3 & 7.6.
Refer to Section 7.9 and 7.11.1.
Refer to Section 7.11.2.
Refer to Section 7.11.3.
Refer to Section 7.11.4.
(1)Stage Properties
"
# STATUS MODE RTEMP ON OFF TIME
1 On Attic Open <ACTIVE>
2 Off Attic Close <ACTIVE>
3 Off Vent Open <CLOSED>
4 On Vent Close <CLOSED>
5 Off Tunnel 1 Open <CLOSED>
6 On Tunnel 1 Close <CLOSED>
7 Off Tunnel 2 Open <CLOSED>
8 On Tunnel 2 Close <CLOSED>
9 Off Natural 1 Open <ACTIVE>
10 On Natural 1 Close <ACTIVE>
11 On Light Ramp
12 On Light Ramp
13 Off Feed Sch1
14 Off Feed Sch2
15 Off Heat 86.0° 77.5° 79.0° None
16 Off Heat 86.0° 77.5° 79.0° None
17 Off Heat 86.0° 77.5° 79.0° None
18 Off Heat 86.0° 75.0° 77.0° None
----------- TARGET 80° ---------
19 Off Cstir 86.0° 82.0° 81.0° Min1
20 Off Cstir 86.0° 82.0° 81.0°
21 Off Cstir 86.0° 82.0° 81.0°
22 Off CNeg 86.0° 82.5° 81.0°
23 Off CNeg 86.0° 82.5° 81.0°
24 Off CNeg 86.0° 83.0° 81.5°
25 On CNegT 86.0° 83.0° 82.0°
26 On CNegT 86.0° 84.0° 83.0°
27 On CTUN 86.0° 84.5° 83.0°
28 On CTUN 86.0° 85.0° 84.0°
29 On CTUN 86.0° 86.0° 85.0°
30 Off CTUN 86.0° 88.0° 86.0°
31 Off CTUN 86.0° 90.0° 88.0°
----------- MAXIMUM TUNNEL FANS ----------
32 Off CEVAP 86.0° 92.0° 87.0° Var
33 Off CEVAP 86.0° 92.0° 87.0° Var
34 Off Off
35 Off Off
36 Off Off
37 Off Off
38 Off Off
39 Off Off
40 Off Off
U1 On NAT CLOSE ---.- 90.0° CLOSED:No
U2 On NAT CLOSE ---.- 90.0° CLOSED:No
U3 On NAT CLOSE ---.- 90.0° CLOSED:No
U4 On NAT CLOSE ---.- 90.0° CLOSED:No
U1 Off NAT OPEN ---.- 92.0° CLOSED:No
U2 Off NAT OPEN ---.- 92.0 CLOSED:No
U3 Off NAT OPEN ---.- 92.0 CLOSED:No
U4 Off NAT OPEN ---.- 92.0 CLOSED:No
--- On Exit Tun ---.- ---- 83.0 ----
--- On Enter Tun ---.- 86.0 ---- ----
Refer to Section 6.4.1, 7.5 & 7.8.
Refer to Section 7.11.6.
Maximum Tunnel Fans: The maximum number
of tunnel fans will be turning ON from this
point downward with hotter temperatures.
Refer to Section 7.11.5.