User Manual

326
────────────────────────────────────────────────────
12.5 INTERFACE Screen (SYSTEM 4)
────────────────────────────────────────────────────
Gateway ON/OFF and IP Address
Set the default gateway (default router).
Turn this ON and specify the IP of the device serving as a gateway when the
8826 communicates with a device (PC) on a network other than its own
network. When the PC is on the same network, use the default gateway of the
PC. When the 8826 is connected one-to-one with a PC or both are connected to
the same hub, a gateway is not necessary. Turn it off.
When DHCP is ON, any gateway information obtained from DHCP has
priority.
DHCP ON/OFF
Set whether to use DHCP.
DHCP enables a device to obtain its IP address or other information
automatically.
When DHCP is ON and a DHCP server is running on the same network, the
8826 obtains its IP address and subnet mask, then is automatically set up.
Any available DNS and gateway information are also obtained. (The
information obtained from DHCP has priority over manually entered settings.)
When DHCP is ON, it automatically sets the subnet mask.
DNS ON/OFF and IP Address
Set DNS.
The IP address is a series of numbers that may be difficult to remember.
Thus, it would be easier to use a name to represent the address.
In a network with a server that searches IP addresses from names, you can
request this server to look up an IP address from a name and thus specify a
device by name and not by address.
There are two such servers: DNS and WINS. The 8826 only supports DNS.
However, these units cannot perform the dynamic registration of names and
IP addresses with DNS.
When DNS is ON, you can specify a device you communicate with by using a
name.
When DHCP is ON, any DNS information obtained from DHCP has priority.
Server (9333)
Specify the PC that runs the 9333 LAN COMMUNICATOR, with which the
8826 communicates. This setting is required for acquiring data using the 9333
LAN COMMUNICATOR.
When specifying with the IP address (when not using DNS), use the IP
address of the PC.
When DNS is ON and you specify the PC with a name, set IP to 0.0.0.0, enter
the host name of the device for which data is being collected in the name field.
When the host name is "collect.hioki.co.jp," for example, do not omit
".hioki.co.jp." Otherwise, your request may not be granted. (Note that the part
shown as ".hioki.co.jp" may vary depending on your network environment.)
When acquiring data using the 9333:
To send measurement data (saved by using the Auto Save function) to the
9333, set Media on Status 1 screen to COMMUNI (LAN). (Real-time transfer of
measurement data is not available.)
To send an Auto Print image to the 9333, set Auto Print destination on Status
1 screen to COMMUNI (LAN).
To send parameter calculation results to the 9333, set Result Save on Status 3
screen to COMMUNI (LAN).
To send a screen image by using the
COPY key, set Copy Destination on
System 4 screen to COMMUNI (interface).