Data Sheet
2
Features
●AC measurement: mean value ●Ancillary functions: auto ranging,
data hold function, auto power save function, battery life warning function
● Display: Max.4199-count LCD ●Sampling rate: 2.5 times/sec (Fast),
1 times/3sec (Slow) ●Measurable conductor diameter: ø33mm
(1.30")
max. ●Maximum rated voltage to earth: CAT III 600 V (Current
measurement section), CAT III 300 V, CAT II 600 V (Voltage measurement
section) ●Max.input current: 2000 A rms cont. ●Max.input voltag:
600 V rms ●Effect of conductor position: within ±5.0 % in any
direction from the center of sensor
■ 3280-10/-20 Specifications (
accuracy at 23˚C±5˚C (73˚F±9˚F), 80% RH or less)
*1. at 420 Ω. (4.2k 0.7V (typ.) 42k to 42M 0.5V (typ.) )
*2. at 420 to 420kΩ. (4.2MΩ ±5.0%rdg.±4dgt. 42MΩ ±10.0%rdg.±4dgt.)
39mm
(1.54")
400g
(14.1oz.)
3282
Safe & Easy Operation!
● Test Lead Holder
for convenient voltage
measurement
Right / Left hand
capability
TEST LEADS HOLDER 9209
(optional)
removable
Light
100g
,
Slim
16mm
(3.5 oz.) (0.63" )
●
Overload protection: DCV/ACV - 600 V DC /AC rms; ohms/continuity
- 250 V AC rms
●
Applicable standards: Safety - EN61010, CAT III
600V(AC A), CAT III 300V, CAT II 600V(AC/DC V) Type A current sensor,
UL 61010B ; EMC - EN61326
●
Drop-proof: 3280-10/-20 can with-stand
a 1m drop onto a concrete floor
●
Location for use: Indoors, altitude up to
2000 m
●
Ambient temperature of use: 0 to 40˚C(32˚F to 104˚F), 80%rh
(no condensation) ●Storage temperature range: -10 to 50˚C (14˚F to
122˚F)
, (no condensation)
●
Power source: CR2032 battery✕1 (3V DC)
●
Continuous operating time: approx. 150 hours (3280-10), 50 hours
(3280-20)
●
Dimensions and mass: Approx. 57 W✕175 H✕16 D mm, 100
g
(Approx 2.2" (W )✕ 6.9" (H)✕ 0.6" (D), 3.5 oz.)
●
Accessories: battery, carrying case, test leads and manual
FUSE
Required
No Fuse
●
PTC Protected
(Non-fuse type)
protects up to 250 V AC/DC
Prevents
careless
mistakes
●
Auto-power save
to conserve battery life
3280-10/-20
●
Options
TEST LEAD HOLDER 9209
Function Range (Accuracy)
AC current
(0.06 ) - 42.00 / 420.0 / 1000 A
(50 to 60Hz: ±1.5%rdg.±5dgt.
(3280-10)
)
(45 to 66Hz: ±1.5%rdg.±5dgt.
(3280-20))
(40 to 45Hz or 66 to 1kHz: ±2.0%rdg.±5dgt. (3280-20))
DC voltage
420.0 m / 4.200 / 42.00 / 420.0 / 600 V
(±1.3%rdg.±4dgt.)
AC voltage
(50 to 500 Hz)
4.200 / 42.00 / 420.0 / 600 V
(±2.3%rdg.±8dgt.)
Resistance
(open terminal voltage 3.4 V max.*
1
)
420.0 / 4.200 k / 42.00 k / 420.0k /
4.200 M / 42.00 MΩ (±
2.0%rdg.
±
4dgt.
*
2
)
Continuity
(
open terminal voltage 3.4 V
max.
)
420.0 Ω (±2.0%rdg.±6dgt.)
(
Buzzer sounds at approx 50 Ω or less
)
Current waveform of the
switching power supply
(primary side)
True RMS method 3280
-20
The 3280-20 performs accurate measurements of even small
currents in the AC 42.00 A range. It also guarantees accuracy of
True RMS measurements for frequencies from 40 Hz to 1 kHz.
MEAN value method 3280-10
●Crest factor: 2.5 max.
(
Applies to input of at least 60% of the range.)
Inspect the unit and check that it is operating correctly before use. When
carrying out measurement on live lines, wear proper protective gear, insulating rubber gloves,
insulating rubber boots and safety helmet, and use extreme caution to avoid electric shock accidents.
WARNING
Includes TEST LEAD 9208 and CARRYING CASE 9398
●Independent-opening double-lever design
●Slim body to allow easy clamping
even for narrow conductors
●Eliminates magnetization-induced heat and
noise, even in heavy-current measurement
●No metal (iron core) exposure, ensuring
enhanced safety
True RMS
In order to prevent short-circuits and injury, use the clamp product on electrical
circuits with a voltage less than the maximum operation circuit oltage.
DANGER