User Manual

4.2 Checking the Connection
46
Setting the nominal voltage
WIRING
U Reference
Select from pull-
down menu
Confirm
Cancel
100 V, 101 V, 110 V, 120 V, 200 V, 202 V, 208 V, 220 V, 230 V,
240 V, 277 V, 346 V, 380 V, 400 V, 415 V, 480 V, 600 V,
VARIABLE
Nominal voltage affects channels 1 to 3.
(Nominal voltage)
Setting the measured frequency
When the display value
is wrong
1. When the voltage or current display value is lower than
expected
The voltage value is low:
Is the voltage clip connected to the power line being tested?
Is the voltage cord inserted in the voltage connector?
The current value is low:
Is the clamp-on sensor inserted in the device’s current connector?
2. When the active power display value is negative
Is the voltage cord of the channel displaying the negative value con-
nected properly?
Is the arrow (printed on the clamp) on the clamp-on sensor for the
channel displaying the negative value pointing to the loaded side?
3. When the voltage display value differs from the expected
value of three-phase connections
Are the phase-to-neutral voltage and line-to-line voltage (voltage cal-
culation methods) selections different?
"Voltage calculation method settings" (page 54)
WIRING
Frequency
Select from pull-
down menu
Confirm
Cancel
50 Hz, 60 Hz
(Measured frequency)