Installation Guide
15
en
Special Case: Manual Cleaning
0
0
4x
Blowing out
•
The Hilti manual pump may be used for blowing out boreholes up to
diameters d
s
≤ 16 mm (5/8") and borehole depths up to
inst
≤ 250 mm
(10") (please contact Hilti for further references).
•
Blow out at least 4 times from the back of the borehole.
Brushing
•
Brush the borehole 4 times with an appropriately sized round steel
brush. See above for details.
Blowing out
•
Blow out at least 4 times from the back of the borehole. See above for
details.
4. Injection of mortar
•
Observe the instructions for use of the dispenser.
•
Check foil pack holder for proper function.
•
Put foil pack into foil pack holder.
•
Do not use damaged foil packs/ holders.
•
Use the static mixer that is delivered with the mortar.
•
Attach the static mixer tightly on to the manifold before starting to dis-
pense.
•
Do not modify the static mixer.
Insert foil pack in foil pack holder
Tightly attach mixer to foil pack manifold