User Manual

Table Of Contents
Thermal Network Bullet Camera User Manual
102
Tolerance Temperature: The device judges whether the triggered alarm stops until
the device temperature/temperature difference is lower than rule temperature by
tolerance temperature. E.g., set tolerance temperature as 3°C, set alarm temperature as
55°C, and set pre-alarm temperature as 50°C. The device sends pre-alarm when its
temperature reaches 50°C and it alarms when its temperature reaches 55°C and only
when the device temperature is lower than 52°C will the alarm be cancelled.
2) Set the alarm rules.
For Point Rule:
a) Click to show the Alarm Rule setting interface.
Figure 9-22 Alarm Rule Settings (Point)
b) Set the alarm rule.
c) Set the Alarm Temperature, Pre-Alarm Temperature, and Tolerance
Temperature.
E.g., select Alarm Rule as Average Temperature is Higher than, and set the Alarm
Temperature to 50 °C, and the device alarms when its average temperature is
higher than 50 °C.
For Line Rule:
a) Click to show the Alarm Rule setting interface.