ADVANCED PARAMETERS
53. Temperature oset
The value to be added to the actual temperature, measured by the sen-
sor (temperature compensation).
Available settings: -1000–1000 (-100–100°C, 0.1°C step)
Default setting: 0 (0
°C )
Parameter size: 2 [bytes]
54. Temperature alarm reports
Temperature alarms reported to the Z-Wave controller. Thresholds are
set in parameters 55 and 56.
Available settings: 0 - temperature alarms disabled
1 - high temperature alarm
2 - low temperature alarm
3 - high and low temperature alarms enabled
Default setting: 0 Parameter size: 1 [byte]
55. High temperature alarm threshold
If temperature is higher than set value, overheat notication will be
sent and high temperature alarm will be triggered (if activated).
Available settings: 1-600 (0.1-60°C, 0.1°C step)
Default setting: 350 (35°) Parameter size: 2 [bytes]
56. Low temperature alarm threshold
If temperature is lower than the set value, underheat notication will
be sent and low temperature alarm will be triggered (if activated).
Available settings: 0-599 (0-59.9°C, 0.1°C step)
Default setting: 100 (10°) Parameter size: 2 [bytes]
NOTE
Value set in parame-
ter 55 must be higher
than value set in pa-
rameter 56.