Installation Instructions

3
Locaon and number of smoke alarms may be specified in relevant regulaons. Where these do not exist, the requirements of DIN 14676 can be used.
Before commencing installaon, ensure all equipment and tools to mount and test the device are available, such as drills, mounng screws (supplied), cables
and ladders.
Smoke alarm are to be used as minimum requirement in all bedrooms, children's rooms and hallways which act as escape routes, and are to be installed
in each case in the middle of the room, on the ceiling only (do not install on wall).
Select the installaon locaon with a minimum distance of 50 cm to surrounding walls, furniture and lamps.
According to German applicaon standard DIN 14676
Locaon Selecon
Equipment
Installaon
2
1
Configuraon is opmal when devices are also located in all other rooms as well as staircases.
In kitchens and wet rooms, smoke alarms are only used when false alarm caused by the characteriscs of these space are excluded.
Please observe the graphics in this guide.
Install smoke alarms as close to the centre of the ceiling as possible, away from light fings and air-condioning ducts. If this is not praccal, put the alarm on the
ceiling, no closer than 50 cm from any wall or corner.
In rooms with ceiling slopes> 20 °, the smoke alarm shall be mounted at least 0.5 m and not more than 1 m away from the ceiling peak.
Ceilings with a slope angle ≤ 20 ° should be treated as horizontal ceiling.
Installaon Locaon
Rooms with sloped ceiling
4
BEDROOM
CHILDRENS
BEDROOM
CHILDRENS
BEDROOM
LIVING ROOM
BATH-
ROOM
KITCHEN
CHILDREN’S
BEDROOM
KITCHEN
WORKSHO
P
BOILER ROOM
LIVING ROOM
BEDROOM
Figure 1 b) Example of the applicaon in a typical single-family house
Figure 1 a) Example of the applicaon in a flat
Hold the coding buon and power the detector on at the same me. The detector will be formaed aer 8 s.
Format