Manual
021-PV200 Rev A PV200 Uses Manual 16
Copyright © High Country Tek, Inc. 2013
PV200 Closed Loop Proportional Valve Controller
Switch the OFF and switch the
ON. The PV200 becomes an
open loop controller. Coil A current is set to the
override current setting of 0.5A.
The Reverse override has a higher priority than the
forward override.
By switching OFF both override inputs, the PV200
resumes normal closed-loop operation and coil B
current is 0.68A because the actual position 0% is
less than the target position 56%.