Process Setup:
Sets the Ramp Rate for both coil A and B to 3 seconds
Up or Down.
Sets the following options to True:
Enable “Enable:” Enable input pin is active
Enable Active High: +12v at the enable input will
enable unit
Ramp to 0 if Disabled: Ramps if disabled
More Current = More speed (This option should be
set True whenever in Dual Coil Valve Driver Mode).
This is forced on in the Dual Coil Valve Driver
mode.
Enable Direction is set to False. The direction is determined by comparing the Command input voltage to the
Center Volts Setting in the Command Range.
All other process options are grayed out and disabled while in Valve Driver mode.
Coil Setup:
Sets Maximum and Minimum Coil Current to 1200mA and
120mA respectively.
In this instance, the Dither has been disabled with a value of
0%.