023-00354-Rev1.6 evc/epc User Manual 25
Copyright © High Country Tek, Inc. 2013
evc/epc Controller
With SAE J1939 Interface
Global Settings
Enable Auto-Reverse (On/Off)
When in HP Management or Anti-Stall
Stop
or No Load RPM, coil A current ramps
down to 0, and then coil B current ramps up
to the Reverse Set- point.
The module will try to restart normal
operation after the reverse cycle completes.
Reverse Time (0 to 65 Sec) It sets the time that coil B will remain in reverse during an Auto-Reverse cycle.
Reverse Retry Count (0 to 65535) The number of times the Auto-Reverse cycle will try to restore normal RPM
before declaring a fault and disabling the unit.
Reverse set-point (0 to 100%) The percentage of Imax output current for coil B during the reverse cycle.
Fixed set-point (0 to 100%)
The percentage of Imax output current for coil A when the measured RPM is above the RPM slow or Max Load
RPM anti-
Recover from loss of signal
When ON automatically recovers and returns to normal operation after the pulse input and the
analog input(s) are back in range.
The evc/epc automatically recovers from a SAE J1939 message timeout error.
The evc/epc automatically recovers when the reference voltages or the supply voltages are outside the
acceptable limits and recover.
The evc/epc will not automatically recover from a coil open or short error.
Hard stop if disabled
ONinput is set to
OFF
OFF or B outputs ramp down to zero when the enable input iOFF