emc-3 Controller Module
User Guide – Rev A
Bank_2_Rev_DYCY 0 100 DYCY for Reverse Fan
Operation
Bank_3_Off_DYCY 0 Start - 1 DYCY to ensure fan is Off
Bank_3_Start_DYCY 0 Max - 1 DYCY for Minimum Fan Speed
Bank_3_Max_DYCY Start + 1 100 DYCY for Maximum Fan Speed
Bank_3_Rev_DYCY 0 100 DYCY for Reverse Fan
Operation
Startup_Delay_Seconds 0 300 Delay from Power on until the
unit will operate fans
Minimum_Fan_Cycle_Seconds 0 300 Minimum time fans can run on
each bank
Bank_1_Fans_Idle_Enable 0 65535 (False = 0, 1 - 65535 = True)
Sets fans to run at min speed
when system is enabled
Bank_2_Fans_Idle_Enable 0 65535 (False = 0, 1 - 65535 = True)
Sets fans to run at min speed
when system is enabled
Bank_3_Fans_Idle_Enable 0 65535 (False = 0, 1 - 65535 = True)
Sets fans to run at min speed
when system is enabled
Engine_Minimum_RPM 0 2500 Minimum RPM for system
enable when EEC1 message is
enabled
HCT_Status_Msg_Enable 0 65535 (False = 0, 1 - 65535 = True)
Sets fans to run at min speed
when system is enabled
Reverse_Dwell_Seconds 0 30 Dwell before fans go to the
Reverse DYCY
Fire_Input_Enable 0 2 (False = 0, 1 = Active Low, 2 =
Active High) Fire Input Enabled
Fan_DG_Input_Enable 0 65535 (False = 0, 1 = Active Low, 2 =
Active High) True = DG Inputs
Enabled
Bank_1_Control_1 0 7 Assignment for control input
Bank_1_Control_2 0 7 Assignment for control input
Bank_1_Control_3 0 7 Assignment for control input
Bank_2_Control_1 0 7 Assignment for control input
Bank_2_Control_2 0 7 Assignment for control input
Bank_2_Control_3 0 7 Assignment for control input