HCT Status Message – enable/disable through the EE-Memory.
This message is multiplexed and alternately sends two data sets;
HCT Status Message
Transmission Cycle Time: 1000mS
Data Length: 8
Data Page: 0
PDU Format: 180
PDU Specific: 0
Priority: 6
Parameter Group Number: 46080 (B400)
Start Position Length Parameter Name
Byte 1 1 Byte
Control Byte for Multiplexed
Message
Byte 2 1 Byte See Mux Table
Byte 3 1 Byte See Mux Table
Byte 4 1 Byte See Mux Table
Byte 5 1 Byte See Mux Table
Byte 6 1 Byte See Mux Table
Byte 7 1 Byte See Mux Table
Byte 8 1 Byte See Mux Table
Data Set 1
HCT State Message Bytes 1
& 2
HCT State Message Bytes 3 &
4
bit Description bit Description
1 DG_1 State 1 EEC1 Message State
2 DG_2 State 2 CM1 FF Message State
3 DG_3 State 3 CM1 00 Message State
4 DG_4 State 4 ET1 Message State
5 DG_5 State 5 IC1 Message State
6 DG_6 State 6 TF Message State
7 DG_7 State 7 Therm1 error State
8 DG_8 State 8 Therm2 error State
9 Coolant Over Temp 9 Therm3 error State
10 Manifold Over Temp 10 Ignition Input State
11 Transmission Over Temp 11 Fire Input State
12 Therm1 Over Temp 12 Reverse Input State
13 Therm2 Over Temp 13 Fans In Reverse Output State
14 Therm3 Over Temp 14
Check Fan System Output
State
15 Fire Detected State 15 Ignition Input Error State
16 System Enabled State 16 Reserved