HES, Inc. Phoenix, AZ 1.800.626.7590 www.hesinnovations.com KS200-640 / KS210-640 Server Cabinet Lock Series Installation Instructions 3085006.002 Rev.
Package Contents Mounting Screws Handling Selectors SFIC Cam Cam Handle DPS Cable Mounting Plate Lock Side Interface Cable Lock Recommended Tools Approved RFID Credential Phillips P2 driver WT-2 Wiegand Test Box Optional Additional Tools: SFIC Core for key override or SFIC Blank Plastic Core Normally Open DPS Switches System Side Interface Cable Specifications Voltage: 12–24V DC ±10% (Power Supply not provided) KS200 / KS210 Current Consumption: Model Input Voltage (V DC) KS200 / KS210 12V DC
Operating Temperature: -10C to 50C Holding Force: 250 lbs 3085006.002 Rev.
Connector Pin Wiring: Molex 8-Pin Connector Pin Wire Color Description 1 Black Ground (RTN) 2 White Wiegand Data 1 / RS485-A* 3 N/A N/A 4 N/A N/A 5 Red +VDC (12V-24V) 6 Green Wiegand Data 0 / RS485-B* 7 Blue LED Input (RED) 8 Yellow LED Input (GREEN) 1 Violet Ground (RTN) 2 Pink Tamper/DPS Contact (N.O.) (+) 3 Gray Lock Control Input (5/12/24 VDC) 4 Tan Tamper/DPS Contact (N.O.
Installation 1. Installing an SFIC Core NOTE 1: A key override (SFIC) provides a backup entry method in the rare case the KS200 or EAC is inactive (Recommended). NOTE 2: The included SFIC cam has been tested with Medeco and Sargent 6- or 7-pin SFIC cores. SFIC Core Cam SFIC Core 6-pin Spacer Cam 6-pin 7-pin 2. INSERT SFIC into lock 1. Insert Cam into SFIC Use the included Spacer with 6-pin SFICs. 2. Preparing the Cabinet 1.
3. Installing the Lock 1. SLIDE lock into cutout. NOTE: (Optional) Install RS485 termination jumper (KS210). (Optional) The DPS signal is closed when the handle is resting in its locked position. The DPS circuit can be extended to include normally open DPS switches arranged in a series to monitor additional doors and panels. DPS Extension Cable Switch #1 (SPST-NO): Provided 2. PERFORM the following to extend the DPS Circuit. a. REMOVE the DPS jumper. b. CONNECT the included DPS extension cable. c.
5. ATTACH rear bracket with screws. 6. ENSURE that the lock is fully secured and flush to the mounting surface in order to depress tamper switch on back of device for correct operation. NOTE: Tamper Switch If the tamper switch is not fully depressed, the lock opens the Tamper/DPS+/- contact. 7. IF the tamper switch is not fully closed, THEN REMOVE the tamper contact, AND ENSURE the lock is closed. 4.
5.
* Round trip loss. V = 2 x I x R x xft xft = V / (2 x I x R) Note: Data 0 and Data 1 wires for Wiegand may be reused for OSDP. However, standard Wiegand cable may not meet RS485 twisted pair recommendations for maximum data transmission speed and distance. Note: For OSDP cable lengths greater than 200 ft (61 m) or EMF interference, install 120Ω termination resistor jumper on the KS210. 3085006.002 Rev.
Connector and Cable Diagram 3085006.002 Rev.
Server Cabinet Wiring Example 3085006.002 Rev.
6. Testing the Lock with the Access Control System 1. TEST the lock with a known good credential to confirm it will open as desired when installed. a. PRESENT a credential known to the EAC. b. LIFT lever and TURN to open the cabinet. 3085006.002 Rev.
This page intentionally left blank 3085006.002 Rev.
Regulatory FCC This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. CAUTION: Any changes or modifications to this device not explicitly approved by the manufacturer could void your authority to operate this equipment.