9292 Jeronimo Road Irvine, CA 92618-1905 SmartID and Smar INSTALLATI Document Number 8030 © 2008 HID GLOBAL CORPORATION.
SmartID Proximity Reader - 8030-901, Rev A.0 SmartID Proximity Reader - 8030-901, Rev A.0 7 Contacts Americas HID Global Corporation (California, USA) Email: tech@hidcorp.com Main: (949) 598-1600 Support: 1-800-237-7769 Fax: (949) 598-1690 Europe, Middle East and Africa HID Global Corporation, Ltd. (Haverhill, UK) Email: eusupport@hidcorp.com Main: +44 (0) 1440 714 850 Support: +44 (0) 1440 711 822 Fax: +44 (0) 1440 714 840 Asia-Pacific HID Global Corporation Asia Pacific Ltd.
SmartID Proximity Reader - 8030-901, Rev A.0 SmartID Proximity Reader - 8030-901, Rev A.0 Contents 6.
SmartID Proximity Reader - 8030-901, Rev A.0 1 Products List This guide is applicable for the following SmartID and SmartTRANS products: HID Part HID Model Description Number *8030xyzz S10 SmartID Mullion Reader *8045xyzz SK10 SmartID Mullion Keypad Reader SmartID Proximity Reader - 8030-901, Rev A.0 6 Regulatory 6.1 UL These proximity readers are intended to be powered from a output of a previously certified power supply. These readers used with listed (UL294) control equipment.
SmartID Proximity Reader - 8030-901, Rev A.0 5.5 Mullion Reader Mounting Plate – Spacer The sizes in the drawing are in millimeters, 1 mm is 0.039 in. SmartID Proximity Reader - 8030-901, Rev A.0 2 Overview The SmartID 13.56MHz and SmartTRANS 13.56MHz + 12 slim door mountable design to match any installation enviro LED’s and buzzer allow the SmartID Readers to be mounte The SmartID reader accepts 5 to 24 Volts DC. The reader o Wiegand, Clock-and-Data (Magstripe ABA / ISO7811), RS2 hardware interfaces..
SmartID Proximity Reader - 8030-901, Rev A.0 3 SmartID Proximity Reader - 8030-901, Rev A.0 Specifications PRODUCT SmartID INPUT VOLTAGE 5-24 VDC POWER Avg 600 mW Peak 1000 mW OPERATING TEMPERATURE CABLE DISTANCE -22° - 140°F (-30° - 60° C) Wiegand 500 ft - 18 AWG (153 m) 300 ft - 20 AWG (91 m) 200 ft - 22 AWG (61 m) Clock-and-Data 82 ft - 22 AWG (25 m) RS232 50 ft (15.24 m) RS485 4000 ft (1,219.2 m) Recommended cable type: Stranded conductor with overall stranded shield or equivalent.
SmartID Proximity Reader - 8030-901, Rev A.0 5.4 Switch Box Mounting Plate - Optional The sizes in the drawing are in millimeters, 1 mm is 0.039 in. SmartID Proximity Reader - 8030-901, Rev A.0 SmartTRANS Indala Prox Avg 1300 m Peak 1600 3.1.1 ISO Card Read Range ISO14443 up to 1.6 in (4 cm) DESFire up to 1.6 in (4 cm) 3.1.2 Interface Inputs EMC Prot. 10K ohm pull-ups Outputs EMC Prot. open drain 0.5 A/max 3.1.
SmartID Proximity Reader - 8030-901, Rev A.0 3.1.4 Reader Output Interface and Pull-up Resistors The SmartID readers provide true open collector outputs for Wiegand, Clock-andData, ABA track 2 emulation, meaning the data output is not voltage driven. External pull-up resistors are required when the controller does not provide internal pull-up resistors. The typical value for the pull-up resistors is 1kOhm. The recommended position to place the pull-up resistors is at the controller side.
SmartID Proximity Reader - 8030-901, Rev A.0 4 5.2 Conductor Connections (All Models) 1 SmartID Proximity Reader - 8030-901, Rev A.
SmartID Proximity Reader - 8030-901, Rev A.0 5 SmartID Proximity Reader - 8030-901, Rev A.0 Installation Instructions 5.1 Wall Mounting Drawing (All Mode 1. Drill two holes for mounting the reader (see Figure 1 Mullion Mounting, page 11). Do not mount readers less than 20 cm (7.87 in) from each other. Make sure that enough room to connect the cable is allowed. Protect the cable against sharp edges and any damage from chaffing. The drawing dimensions are in millimeters. 1 mm equals 0.039 inch 2.