If the corrosion inhibitor tests low, add one 8 oz. container of Cryo-Tek inhibitor for every 20 gallons of system
uid capacity. If the total system capacity is less than 20 gallons, add one 8 oz. container of Cryo-Tek Inhibitor.
If after inhibitor addition and thorough system mixing, the corrosion inhibitor still tests low, add another 8 oz.
container of Cryo-Tek inhibitor for every 20 gallons of system capacity. If, after this addition, the inhibitor still
tests low, the system should be drained, cleaned and recharged with fresh Cryo-Tek.
Remember to always check with the boiler manufacturer for correct glycol levels.