Datasheet

Detail mass
Box walls
Operating and ambient conditions
Application area Suitable for indoor installation and outdoor installation, protected
against weather influences
Ambient temperature Maximum value + 40 °C
Minimum value - 25 °C
Fire protection in the event of internal faults Demands placed on electrical devices from standards and laws
Minimum requirements
- Glow wire test in accordance with IEC 60695-2-11:
- 650°C for boxes and cable glands
- 850°C for parts of insulating material necessary to retain current
carrying parts in position
Burning behaviour Glow wire test IEC 60695-2-11: 750 °C
UL Subject 94: V-2
flame-retardant
self-extinguishing
Degree of protection against mechanical load IK07 (2 Joule)
Toxic behaviour halogen-free
silicone-free
"halogen-free" in accordance with the examination of the cables
and insulated wires - corrosiveness of fumes - as per IEC 60754-2
Note: For material properties see technical data.
With or without terminals
DK 0200 G
Page 2 of 3
Gustav Hensel GmbH & Co. KG * Gustav-Hensel-Str. 6 * 57368 Lennestadt * Germany * Telefon: +49 (0)2723/609-0 * Fax: +49 (0)2723/60052 * Date: March 6. 2020