Instruction Manual

28
Model: Touch Carbon
Optional Settings - Feature Table
FEATURE
Viewing Accessory
Pairing Accessories
Temperature Format
Switching Differential
Output Delay
Up/Down Temperature Limit
Sensor Selection
Floor Temperature Limit
Optimum Start
Rate of Change
Program Mode
(DST) Daylight Saving
Communications ID
(Modbus)
Program Type
DESCRIPTION
Information only
Commences countdown from 99 00 seconds.
00 = °C, 01 = °F (00 = Default)
00 = 0.5°C, 01 = 1.0°C (Default) 02 = 2.0°C, 03 = 3.0°C
00 - 15 M
inutes (00 = Default)
00° - 10°C (00° = Default)
00 = Built in Sensor with optional wireless Remote Air (Default)
01 = Wireless Remote Air Only
02 = Floor Sensor Only
03 = Built in + Floor Sensor + optional wireless Remote Air
04 = Floor Sensor + Wireless Remote Air Only
20°C 45°C (28°C Default)
00 = Disabled (Default) 01 = 1 Hour 02 = 2 Hours
03 = 3 Hours 04 = 4 Hours 05 = 5 Hours
Information Only
00 = 5/2 01 = 7 Day 02 = 24 Hour
03 = None programmable
00 = Disabled (D
efault) 01 = Enabled
01-32
00 = Disabled
00 = 4 Comfort Levels (Default) 01 = 6 Comfort Levels
SETTING
A
P
01
Menu
Entry Point
02
03
04
05
06
07
08
09
10
11
12
13
Back-light Dimming
00 = Medium 01 = Low