Installation and Operation Manual

8WirelessSNRInstallationandOperationManual
059049-00 Rev. ' HeatͲTimerCorp.
DetailedOperation
ControlTheory
TheHeatͲTimerWirelessNetworkSensorSystemisdesignedtobeusedinavarietyof largebuildings,gardenapartments,andin
retrofitapplications.Thisgivesboththeaccuracyandflexibilityrequiredtomonitorthosebuildings'temperatures(givingthecontrol
morepowertosavefuelwhilekeepingspacetemperaturesatcomfortable
levels).Thesystemeasestheinstallationofspacesensors
inbuildingswereitwouldbedifficultorcostprohibitiveutilizingother means,andgivesHeatͲTimerPlatinumcontrolsaccesstothe
wirelesssensordata,whichitlogsandusesformonitoringandfineͲtuningitsoperation.
Theprimaryintegralcomponentsof
thesystemare:theMSIHub,Transceivers(TRV),WirelessSensors(SNR),andWireless
Temp erat ureModules(WTM).TheSNRscommunicatetheirinformationtoanearbyTRVordirectlytoanMSIHub.Datareceivedbya
TRVistransmittedeithertoanotherTRVortotheMSIHub.Alldatareceived
bytheMSIHubiscommunicatedtothePlatinumcontrol.
Troubleshooting
Symptom PossibleCause RecommendedAction
BothredstatusLEDs(orallthreeLEDs)are
continuouslyblinking.
SystemIDhasnotbeenconfigured. ConfiguretheSystemID.IftheLEDsare
stillblinkingaftertheSystemIDhasbeen
configured,contactCustomerSupport.
StatusLEDs arenotblinkingafterthe
batteriesareinstalled.
Batteriesnotinstalledcorrectly,orare
weakordrained.
Verifythebatteriesaregoodandare
installedcorrectly(check thepolarity
diagramonthebase).
SystemIDisalreadyconfigured. Ifthe SystemIDhasbeenpreviously
configuredandisknown,noactionis
required.
IftheSystemIDisnotknown,reconfigure
theSystemID.
Dataisnotbeing
transmittedorreceived
bytheWirelessSNR.
Batteriesweakordrained. ReplacebothAAalkalinebatteries
(HeatͲTimerp/n020008Ͳ00).