Specification Sheet

The Saf-T Vent
®
SC is a concentric vent system
designed for zero clearance installation in residential
and light commercial applications. It is approved for
use on ANSI Category I, II, III, and IV Gas-Burning
Appliances, and Direct Vent or Sealed Combustion
Appliances as approved by the appliance manufacturer.
The Saf-T Vent SC factory-built Special Gas Vent and
Gas Vent Connector is Tested and Listed by
Underwriters Laboratories to UL 1738/ULC S636 and
is for use with Listed natural gas or propane burning
equipment. The system is to be installed and sealed
per the manufacturers’ instructions so the flue gas
conduit is gas tight, preventing leakage of products of
combustion into a building.
Saf-T Vent SC is a double-wall product that consists of
a flue-gas conduit fabricated from AL 29-4C
®
, which is
ideal for use with modern gas-burning equipment that
may produce excessive amounts of condensation in
the vent. The outer jacket of the system is constructed
from stainless steel with a space of approximately one
inch between the flue-gas conduit and the jacket.
Some appliances are Listed to utilize the space
between the flue-gas conduit and the outer jacket for
combustion air supply. This design allows exhaust
and air intake to occur through a single penetration
through the building structure.
All joints in the Saf-T Vent SC system have a
“straight-seal” design, and are equipped with a
factory-applied seal. The outer jacket is secured with
three stainless steel screws. This closure system is
tested to be gas tight at two and one-half times the
Listed pressure rating of eight (8) inches water column.
When connected to gas-burning appliances with a
maximum continuous flue-gas temperature rating of
550°F/288°C, Saf-T Vent SC may be installed
unenclosed, or within a non-combustible chase or joist
bay, or within a vertical combustible enclosure at zero
(0”) clearance (maximum 30 degrees offset).
When connected to gas-burning appliances with a
maximum continuous flue-gas temperature rating of
330°F/166°C, Saf-T Vent SC may be installed within a
combustible horizontal enclosure (joist bay) at zero
(0”) clearance.
When connected to gas-burning appliances with a
maximum continuous flue-gas temperature rating of
400°F/204°C, Saf-T Vent SC may be installed within a
combustible horizontal enclosure (joist bay) at one
inch (1”) clearance.
The Saf-T Vent SC system is to be sized and installed
only in accordance with appliance manufacturers’
specifications, the most current edition of NFPA 211
Standard for Chimneys, Fireplaces, Vents, and Solid
Fuel-Burning Appliances, the most current edition of
NFPA 54 National Fuel Gas Code (ANSI Z223.1) or
CSA B 149.1, and any other applicable local, regional,
and national codes.
©2003 Heat-fab, Inc. Product Specifications subject to change
without Notice. All Rights Reserved. Saf-T Vent is a registered
trademark of Heat-fab, Inc. AL 29-4C is a registered trademark
of ATI Properties, Inc..
www.heat-fab.com 130 Industrial Blvd., Turners Falls, MA 01376
Pub #11467-110703
Saf-T Vent
®
SC Specifications for Special Gas Vent Applications,
Reduced Clearance Installations, and Approved Sealed Combustion Appliances
TECHNICAL SPECIFICATION
Product Saf-T Vent SC Special Gas Vent
and Gas Vent Connector
Uses Vents (Horizontal or Vertical) for
Gas-Burning Appliances, suitable for
ANSI Category I, II, III, and IV
Gas-Burning Appliances, certain
Direct Vent Appliances, and approved
Sealed Combustion applications.
Fuels Natural gas or propane fired equipment
Pressure Positive up to 8" wc, negative, or neutral
Standard
Diameters 3", 4"
Lengths 12", 24", 36", and Adjustable
Elbows 45° and 90°
Fittings Complete range of Adapters,
Terminations, and Accessories
Flue-Gas AL 29-4C
®
stainless steel
Conduit
Jacket Stainless steel