User Guide
6
• Donotaddadditionaloiltomotorsunequippedwithoil
tubes. The compressor is hermetically sealed at the
factory and does not require lubrication.
START UP & ADJUSTMENTS
Pre-Start Check List
√ Verify the unit is level and has sufficient clearances for
unobstructed airflow.
√ Verify the outdoor coil and top of the unit are free from
obstructions and debris, and all equipment access/
control panels are in place.
√ Verify that the line voltage power leads are securely
connected and the unit is properly grounded.
√ Verify that the low voltage wires are securely connected
to the correct leads on the low voltage terminal strip.
√ Verify that the power supply branch circuit overcurrent
protectionissizedproperly.
√ Verify that the thermostat is wired correctly.
Start-Up Procedures
WARNING:
This unit is equipped with a crankcase heater.
Allow 24 hours prior to continuing the start up
procedures to allow for heating of the refrigerant
compressor crankcase. Failure to comply may
result in damage and could cause premature
failure of the system. This warning should be
followed at initial start up and any time the power
has been removed for 12 hours or longer.
Air Circulation - Indoor Blower
1. Set the thermostat system mode on OFF and the fan
mode to ON.
2. Verify the blower runs continuously. Check the air delivery
at the supply registers and adjust register openings for
balanced air distribution. If insufficient air is detected,
examine ductwork for leaks or obstructions.
3. Set the thermostat fan mode to AUTO and verify the
blower stops running.
System Cooling
1. Set the thermostat’s system mode to COOL and the
fan mode to AUTO. Gradually lower the thermostat
temperature setpoint below room temperature and
verifytheoutdoorunitandindoorblowerenergize.
2. Verify blower wheel is spinning in direction indicated by
arrow. Feel the air being circulated by the indoor blower
and verify that it is cooler than ambient temperature.
Listen for any unusual noises. If unusual sounds occur,
determine the source of the noise and correct as
necessary.
3. Verify HI and LO refrigerant pressures.
NOTE: If refrigerant pressures are abnormal and the
compressor is rotating backwards, shut off main power to
the unit and switch any two field wires at the disconnect.
DO NOT alter unit wiring.
4. Allow the system to operate for several minutes and then
set the temperature selector above room temperature.
Verify the fan and compressor cycle off with the
Optional Equipment
Optional equipment requiring connection to the power
or control circuits must be wired in strict accordance
with current provisions of the NEC (ANSI/NFPA 70),
with applicable local codes having jurisdiction, and the
installation instructions provided with the equipment.
Optional Equipment (low ambient control, hard start kits,
etc.) should be installed in strict accordance with the
manufacturer’s installation instructions
Transformer Upgrade Kit
If this 2-stage heat pump is installed in conjunction with
a gas furnace and fossil fuel kit, the furnace transformer
MUST be upgraded to one with a 60 VA rating or using
the transformer upgrade kit (904077). To upgrade the
transformer:
• Removetheexistingtransformerandinstallthenew
60 VA transformer.
• Removethe3ampfuseonthefurnacecontrolboard
and install the 5 amp fuse provided.
NOTE: The new transformer may be larger than the
existing transformer that is mounted in the furnace. If this
happens, mount the 60 VA transformer using one of the
mounting holes in the furnace panel. On the other side
either drill a 0.149 hole in the panel and use the existing
fastener, or use a self-drilling fastener to secure the other
side of the transformer.
HEAT PUMP MAINTENANCE
WARNING:
To prevent electrical shock, personal injury, or
death, disconnect all electrical power to the unit
before performing any maintenance or service.
The unit may have more than one electrical
supply.
Proper maintenance is important to achieve optimum
performance from the heat pump. The ability to properly
perform maintenance on this equipment requires certain
mechanical skills and tools. If you do not possess these
skills, contact your dealer for maintenance. Consult your
local dealer about the availability of maintenance contracts.
Routine maintenance should include the following:
• Inspectandcleanorreplaceairltersatthebeginning
of each heating and cooling season, or more frequently
if required.
• Inspecttheoutdoorcoilatthebeginningofeachcooling
season. Remove any debris. Clean the outdoor coil
and louvers as necessary using a mild detergent and
water. Rinse thoroughly with water.
• Inspecttheelectricalconnectionsfortightnessatthe
beginning of each heating and cooling season. Service
as necessary.
CAUTION:
The unit should never be operated without a
filter in the return air system. Replace disposable
filters with the same type and size.










