CXM Control Start-up Operation
The control will not operate until all inputs and safety
controls are checked for normal conditions. The
compressor will have a 5 minute anti-short cycle delay
at power-up. The first time after power-up that there is a
call for compressor, the compressor will follow a 5 to 80
second random start delay. After the random start delay
and anti-short cycle delay, the compressor relay will
be energized. On all subsequent compressor calls, the
random start delay is omitted.
T-stat signal
HRH/HRV
PSC fan
G Fan only
G, Y or Y1 Stage 1 heating
5
G, Y1, Y2 Stage 2 heating
5
G, Y1, Y2, W N/A
G, W Emergency heat
G, Y or Y1, O Cooling
6
G, Y1, Y2, O N/A
1 Stage 1 = compressor, fan
Stage 2 = compressor, auxiliary electric heat, fan
2 Cooling = compressor, fan, reversing valve
Table 6b: Unit Operation