Quick Start Manual
6
around penetrations into the air handler, such as for 
electrical wiring.
Air Filters
 WARNING:
Never operate the air handler without a filter 
or with doors removed. Dust and lint can build 
up on internal components, resulting in loss of 
efficiency, equipment damage, and possible fire.
HMB Series air handlers are not equipped with filter 
racking; however, it is strongly recommends that a filter 
be located in the return air duct system. Installing the filter 
and replacing it every 3 months will increase air quality 
throughout the home.
Unconditioned Spaces
All duct work passing through unconditioned space must 
be properly insulated to minimize duct losses and prevent 
condensation. Use insulation with an outer vapor barrier. 
Consult your Distributor for the recommended type and 
thickness of insulation for your area as required by local 
codes.
Condensate Drainage
 CAUTION:
The air handler must be level to ensure proper 
condensate drainage. An unlevel installation 
may result in structural damage, premature 
equipment failure, or possible personal injury.
• Toensurepropercondensatedrainage,theunitmust
be installed in a level position within 1/4 inch over the 
height, width, and depth of the unit. The best system 
performance will be obtained if the unit is located in a 
centralized position with respect to the air distribution 
system. Refer to the Installation Instructions supplied with 
the cased coil for proper condensate drain connections.
• Iftheairhandlerislocatedinorabovealivingspace
where damage may result from condensate overflow, 
an auxiliary drain pan should be installed under the unit. 
A separate drain line should extend from the pan to a 
conspicuous point and serve as an alarm indicating 
that the primary drain is restricted. As an alternative to 
a separate drain line, an approved water level indicator 
or float switch device should be used to shut down the 
unit in the event water is detected in the auxiliary pan.
• During system checkout, inspect the drain line and
connections to verify proper condensate drainage.
• Methodsfordisposingofcondensatevaryaccording
to local codes. Refer to local codes or authority having 
jurisidiction for restrictions and proper condensate 
disposal requirements.
AIR HANDLER INSTALLATION
The HMB Series air handler is shipped ready for vertical 
upflow installation and is approved for attic, basement, 
alcove/closet or crawlspace installation with zero clearance 
to combustibles. They may also be applied in downflow 
or horizontal left and right discharge applications. See 
Table 1 (page 4) for required installation clearances. This 
appliance is approved only for indoor use.
NOTE: For shipping purposes, the front and rear joining 
brackets are located in the unit’s heater box. Remove 
these two items from the heater box before beginning.
• Theunitmustbeleveledatinstallationandattachedto
a properly installed duct system.
• Thesurfacethattheairhandlerismountedonmust
provide sound physical support of the unit.
• Theairhandlermustbeinstalledsothatallelectrical
components are protected from water.
• Ifalouvereddoorisinstalledacrossthefrontofthis
unit, the appliance must be mounted flush or behind 
front edge of finished wall.
• Modular air handlers are intended to be mated 
with specific cased coils. Reference the Technical 
Specifications for coil mating combinations.
Upflow Installation
The HMB Series air handler is shipped from the factory 
ready for upflow configuration as shown in Figure 1 (page 
7). Return air must must enter from the bottom of the unit.
1. Remove the bracket above the door of the cased coil. 
Retain the screws for later use. NOTE: Before mating 
the modular unit with the cased coil, clean the mating 
surfaces on both units and apply the black neoprene 
gasket tape to the top of the coil case (except the rear 
surface). Make sure there are no gaps on the front and 
side flanges.
2. Carefully place the modular air handler on top of the 
cased coil making sure not to damage the cased coil 
flanges. The units will be flush in front with an overhang 
in the back as shown in Figure 2 (page 7).
3. Remove the lower front bracket (Figure 3, page 7) from 
the modular unit. Retain the screws for later use.
4. Attach the front joining bracket to the front of the modular 
unit. Align the screw holes in the bracket with the holes 
from the lower front bracket and the top panel of the 
coil case. See Figure 3.
5. Secure the bracket with the screws removed earlier in 
steps 1 & 2.
6. Attach the rear joining bracket to the backside of the 
modular unit and cased coil. Position the bracket so that 
it is flush with the sides and back of the units with the 
1/2” insulation facing the rear gap between the units.
7. Secure the rear bracket with self tapping screws.










