Quick Start Manual
3. Remove horizontal drain pan retaining clip (1-screw).
4. Carefully remove coil assembly and bottom drain pan.
5. Move horizontal drain pan from left hand side of coil to 
right side.
6. Install modied coil assembly back into unit.
7.  Reinstall  coil  support  bracket  and  horizontal  drain  pan 
retaining clip.
8. Determine drain holes being used and reposition knockout 
caps.
9. Reinstall doors.
E. Electric Furnace
Optional electric heating packages are available, see the unit label 
for various sizes.
* See Electric Heater Kit Specications Table
F. Power Wiring
Refer to the unit’s nameplate for specic electrical data.
Use copper conductors only. Tighten all wire connectors. 
Refer to unit nameplate for minimum circuit ampacity. For correct 
wire size, refer to the National Electrical Code. Use 75˚C minimum 
wire in unit wiring compartment.
G. Control Wiring
Field connections  are made  to the  low voltage  terminal strip. 
Consult  installation  instructions  provided  with  accessory items 
for specic information on control wiring. Use 18 AWG minimum 
copper control conductors for control wiring up to 50 feet between 
units. 16 AWG control conductors are recommended for lengths up 
to 100 feet. Class 2 wiring is acceptable. Do not short control leads. 
Transformer burn-out will result. Set thermostat heat anticipator at 
0.15 amps for air handler.
H. Blower Motor
Units are equipped with a three-speed blower motor. Two factory-
selected motor speed leads are connected to the fan relay (FR) to 
provide automatic  speed  change for  heating  and cooling  airow 
volumes. The pre-selected motor speeds would normally not have 
to be changed in the eld. All HAH models contain a post purge 
timer (TDR) that delays the blower turning off at the end of the
cooling cycle, this improves energy efciency.
Terminal  number  4  on  the  (FR)  fan  relay  is  the  cooling  blower 
speed  and  terminal  number  6  on  the  (FR)  is  the  heating  blower 
speed.
I. Refrigerant Piping
All air handlers have DX refrigerant cooling coils installed, liquid 
and suction piping should be sized in accordance with condensing 
unit manufacturer’s recommendations. An adapter (by others) may 
be  required  to  make  the  transition  between  the  line  set  and  the 
coil connector. The evaporator coil has sweat copper connections. 
The suction line is a swaged solder cup connection. The liquid line 
connection is made to a tail piece portion of the TXV. Remove the 
nut on the inlet to the expansion valve and place it on the tail piece 
prior  to  brazing  the  liquid  line.  DO  NOT  connect  the  tail  piece 
to the TXV until the liquid line has been brazed to the tail piece. 
Refrigerant  lines  should  be  soldered  with  silver  solder  or  other 
high temperature brazing alloy. Dry nitrogen must ow through the 
refrigerant lines during the brazing operation to prevent oxidation.
J. Refrigerant Flow Control
As  shipped,  the  TXV  installed  on  the A-coil  is  for  the  nominal 
capacity  of  a  13  SEER  matched  with  Heat  Controller,  Inc., 
condensing units. The TXV is for use on an R-410A system. For 
other  refrigerants,  contact  the  factory. TXV has  a  built-in  check 
valve for reverse ow and is suitable for heat pump operation. All 
are externally  equalized  with  non-adjustable superheat and  have 
15% bleed. Hard start capability for outdoor units is not normally 
required when a 15% bleed valve is used. The external equalizer 
line attached to the TXV has a female are nut and is attached to 
the suction line at the coil. Install the TXV bulb to the suction line 
using the  bulb clamp furnished with the kit. The bulb should be 
installed on a horizontal run of the suction line if possible. On a 
line less than 7/8” OD, the bulb may be installed on top of the line. 
With 7/8” OD or over, the bulb should be installed in a position of 
about 4 or 8 o’clock. If the bulb installation is made on a vertical 
run,  the  bulb  should  be  located  at  least  6  inches  from any  bend 
and on the tubing side opposite the plane of the bend. On vertical 
bulb  installations,  the  bulbs  should  be  positioned  with  the  bulb 
capillary tube at the top. The bulb must be insulated using thermal 
insulation to protect it from the effects of the surrounding ambient 
temperature.
CAUTION
IT IS MANDATORY TO USE AN
EMERGENCY AUXILIARY DRAIN PAN
WITH ANY COIL OR AIR HANDLER
INSTALLED IN AN ATTIC OR ABOVE A
FINISHED CEIING!
CAUTION
DISCONNECT POWER AT MAIN FUSE OR CIRCUIT 
BREAKER DISTRIBUTION PANEL BEFORE WIRING 
UNIT TO PREVENT SHOCK OR FIRE HAZARD.
NOTE: SEE UNIT FOR COMPLETE WIRING DIAGRAM 
LOCATED ON BLOWER HOUSING.
2







