Quick Start Manual
A. Introduction
Heat Controller, Inc., Air Handlers come in a variety of models and 
sizes for upow or horizontal use and when combined with cool-
ing coils, are ready for air conditioning and heat pump applications. 
These instructions are primarily to assist qualied individuals trained 
and experienced in the proper installation of this type of equipment.
B. Rules for Safe Installation and Operation
1. Read these rules and the instructions carefully. Failure 
to follow the rules and the instructions could cause a 
malfunction of the unit, and a possible safety hazard. 
Keep these instructions nearby the unit for future 
reference.
2. This unit has been designed and manufactured to comply 
with National Codes; however, it is the installer’s 
responsibility to install this unit to comply with 
prevailing codes and regulations. Heat Controller, Inc., 
assumes no responsibility for units installed in violation 
of any code or regulation.
3. Before servicing, ALWAYS SHUT OFF 
ELECTRICITY TO THE UNIT. This will prevent any 
electrical shocks.
4. Ground the unit to prevent electric shock. All electrical 
wiring should be in accordance with the National 
Electrical Code.
5. Duct work must be installed in accordance with the 
standards of the National Fire Protection Association 
(NFPA) for the installation of Air Conditioning, Warm 
Air Heating and Ventilating Systems (NFPA 90A and 
90B). The air distribution duct system should be sized for 
0.2 inches of static pressure. See National Environmental 
Systems Contractors Association Manual K for duct 
sizing recommendations. Ductwork in non-conditioned 
spaces must be insulated to prevent formation of 
condensate and for maximum operating efciency.
6. The safety testing agency label appearing on the unit 
covers the unit and factory installed coil(s) only. It does 
not cover any other equipment.
7. Exterior surface of cabinet may sweat when unit is installed 
in non-conditioned space such as attic or garage. Installer 
must provide protection such as full size auxiliary drain 
pan on all units installed in non-conditioned space such as 
attic or garage type installations to prevent damage from 
condensation. It is recommended that units installed in 
non-conditioned space be insulated on the outside with 1” 
thick berglass with the vapor barrier on the outside.
8. While designed to operate quietly when properly installed, 
several steps should be taken to insure this. Use of 
isolation pads when mounting unit, exible duct collars 
for discharge, and use of acoustical duct liners are all 
good installation practices that promote quiet operation.
9. Cabinet insulation is rated for R=4.2 (standard). Some 
jurisdictions require R=6.0 on installations in non-
conditioned space. Add insulation 1” thick to exterior of 
air handler to comply in these jurisdictions, putting the 
vapor barrier on the outside.
C. Unpacking the Unit
The unit should be unpacked on receipt and if damage is found, 
a claim should be made immediately to the shipping carrier. This 
is the responsibility of the entity receiving the equipment. The air 
handler is completely assembled, as received. Electric power, ther-
mostat wiring, refrigerant piping and duct connections are needed 
to complete an installation. Additionally, a drain connection will 
be needed.
Check the  rating  plate for  unit  size, voltage,  phase  etc. to  make 
sure unit meets your requirements.
D. Physical Installation
MINIMUM CLEARANCES
These units have a 0” minimum clearance to combustible materi-
als rating from all  cabinet  surfaces. The unit should be  installed 
with serviceability clearance of 30” from the front of the unit. The 
unit can be serviced entirely from the front, including replacing the 
lter. Be sure and route primary and secondary drain connections 
so as not to obstruct lter replacement.
ARRANGEMENT
Unit is shipped from the factory arranged to be installed in a verti-
cal upow or horizontal right to left airow position (standard) or 
eld convertible to a horizontal left to right airow position.
Upow Application
In  an  upow  installation  the  discharge  outlet  is  at  the  top.  Care 
should be taken to ensure unit is level to permit proper condensate 
drainage. Normal upow installation will be in a basement or clos-
et. If installed in a closet, the closet should have a platform framed 
in, with an opening on top of the platform centered in the closet. 
Connect the supply air outlet to a discharge air plenum. Install re-
turn air grilles from outside the closet to space below the platform. 
Platform must be at least 10” above the oor. Run all supply and 
return ductwork in accordance with local codes.
Horizontal application
Horizontal application will normally be used in an attic or crawl 
space. This type installation requires a return air duct be attached 
to  the  air  handler  inlet.  The  opposite  end  of  the  return  air  duct 
is attached to a return air lter grille through the ceiling or wall. 
Remove lter from unit if lter grill is used. The unit is shipped in 
right to left conguration. 
FOR LEFT TO RIGHT APPLICATIONS.
1. Remove and set aside front panels.
2. Remove the coil support bracket (4-screws).
CAUTION
A “P” trap must be installed in the coil
drain line! Cap unused drain ttings.
WARNING
To ensure unit will not interfere with drains and 
refrigerant lines, modication must be made 
prior to installing these lines..
1







