Installation, Operation & Maintenance  WDG AIR HANDLER SERIES  Heat Controller, LLC
 WARNING! 
WARNING! These instructions are intended as 
an aid to qualifi ed licensed service personnel for 
proper installation, adjustment and operation of 
this unit. Read these instructions thoroughly before 
attempting installation or operation. Failure to follow 
these instructions may result in improper installation, 
adjustment, service or maintenance possibly resulting in 
property damage, personal injury or death.
For continuing high performance and to minimize possible 
equipment failure, it is essential that annual maintenance be 
performed on this equipment. Consult your local dealer as to the 
availability of a maintenance contract.
Air Filter
Check the system fi lter every ninety days or as often as found to 
be necessary and if obstructed, clean or replace at once.
IMPORTANT: Do not operate the system without a fi lter in place.
Indoor Coil - Drain Pipe - Drain Line
Inspect the indoor coil once each year for cleanliness and clean 
as necessary. In some cases, it may be necessary to remove the 
fi lter and check the return side of the coil with
a mirror and fl ashlight.
IMPORTANT: Do not use caustic household drain cleaners 
or bleach in the condensate pan or near the indoor coil. Drain 
cleaners will quickly damage the indoor coil.
MAINTENANCE
Unit & System Checkout
 WARNING! 
After installation has been completed, it is recommended that the 
Air Handler be checked against the following checklist:
CHECKOUT PROCEDURE
❑  Power: Make sure power is “OFF” at power disconnect 
switch.
❑  Field Wiring: Check all fi eld wiring for tight connections. 
See that grounding of unit is in accord with code
❑  Unit Suspension: Make sure unit suspension (if used) 
is secure and that there are no tools or loose debris in, 
around or on top of the unit.
❑ 
Ducts: Check all duct outlets; they must be open and 
unrestricted.
❑  Drain Lines: Check drain lines and be sure all joints are 
tight.
❑ 
Drain Pan: Make sure secondary drain pan is installed.
❑  Power Supply: Check power supply for correct 
requirements per unit nameplate.
❑  Filters: Check fi lters for proper size. Inform owner of 
proper procedure for removal and reinstallation.
❑  Operation: Energize the system and carefully observe 
its operation; make any necessary adjustment.
❑  Procedure: Instruct owner, engineer (if possible) on 
proper operating procedure and leave Use and Care 
Manual with owner.
WARNING! Electrical shock hazard - Lock unit disconnect 
switch in open position before servicing unit. Failure 
to follow this warning could result in property damage, 
personal injury, or death.