Quick Start Manual
13
Installation, Operation & Maintenance  WDG AIR HANDLER SERIES  Heat Controller, LLC
Electrical - Thermostat Wiring
 CAUTION! 
 CAUTION! 
CAUTION! Many units are installed with a factory or fi eld 
supplied manual or electric shut-off valve. DAMAGE WILL 
OCCUR if shut-off valve is closed during unit operation. A 
high pressure switch must be installed on the heat pump side 
of any fi eld provided shut-off valves and connected to the 
heat pump controls in series with the built-in refrigerant circuit 
high pressure switch to disable compressor operation if water 
pressure exceeds pressure switch setting. The fi eld installed 
high pressure switch shall have a cut-out pressure of 300 psig 
and a cut-in pressure of 250 psig. This pressure switch can 
be ordered from the manufacturer with a 1/4” internal fl are 
connection as part number 39B0005N02.
CAUTION! Refrigerant pressure activated water regulating 
valves should never be used with the manufacturer’s equipment.
Thermostat Installation
The thermostat should be located on an interior wall in a 
larger room, away from supply duct drafts. DO NOT locate the 
thermostat in areas subject to sunlight, drafts or on external 
walls. The wire access hole behind the thermostat may in certain 
cases need to be sealed to prevent erroneous temperature 
measurement. Position the thermostat back plate against the 
wall so that it appears level and so the thermostat wires protrude 
through the middle of the back plate. Mark the position of the 
back plate mounting holes and drill holes with a 3/16” (5mm) bit. 
Install supplied anchors and secure plate to the wall. Thermostat 
wire must be 18 AWG wire. Wire the appropriate thermostat as 
shown in Figures 6 and 7 to the low voltage terminal strip on 
the ECM control board. Practically any heat pump thermostat 
will work with these units, provided it has the correct number of 
heating and cooling stages.
Figure 7: Three Heat / Two Cool, Auto / Manual 
  Changeover Programmable (7 Day) - Non-
  Programmable, With Humidity Control
Units with ECM Fan
Figure 6: Three Heat / Two Cool, Manual / Auto
 Changeover Programmable
Units with ECM Fan
Field Wiring
Factory Wiring
Field Wiring
Factory Wiring
See equipment wiring diagram for more details.
See equipment wiring diagram for more details.
Notes:
1) ECM dehumidification mode slows down fan speed in the
cooling mode when dehumidification output from thermostat is
active. Normal heating and cooling fan speeds are not
affected.
2) ECM board DIP switch SW9 must be in dehumid. mode.
ATP32U03 Thermostat
Connection to ECM Control
Compressor
Compressor Stage 2
Reversing Valve
Fan
24Vac Hot
24Vac Common
Fault LED
Y1
Y2
O
G
R
C
L
Y1
Y2
O
G
R
C
AL1
ECM
Electric Heat
W1
W
ATP32U04 Thermostat
Connection to ECM Control
Compressor
Compressor Stage 2
Reversing Valve
Fan
24Vac Hot
24Vac Common
Fault LED
Electric Heat
ECM
Y1
Y2
DH
O
G
R
C
AL1
Y1
Y2
DH
O
G
R
C
L
W1
W
Dehumidification