Quick Start Manual
33
Installation, Operation & Maintenance  HTV/HTD/HTH SERIES  Heat Controller, Inc.
Unit Start-Up Procedure
pressure drop across the heat exchanger versus the data 
in Tables 9a through 9b. Heat of rejection (HR) can be 
calculated and compared to catalog data capacity pages.  
The formula for HR for systems with water is as follows:
HR = TD x GPM x 500, where TD is the temperature 
difference between the entering and leaving water, 
and GPM is the fl ow rate in U.S. GPM, determined by 
comparing the pressure drop across the heat exchanger 
to Tables 9a through 9b.
f. 
Check air temperature drop across the air coil when 
compressor is operating. Air temperature drop should be 
between 15°F and 25°F [8°C and 14°C].
g.  Turn thermostat to “OFF” position. A hissing noise 
indicates proper functioning of the reversing valve.
6. Allow fi ve (5) minutes between tests for pressure to equalize 
before beginning heating test.
a.  Adjust the thermostat to the lowest setting. Place the 
thermostat mode switch in the “HEAT” position.
b.  Slowly raise the thermostat to a higher temperature until 
the compressor activates.
c.  Check for warm air delivery within a few minutes after the 
unit has begun to operate.
d.  Refer to Table 10. Check the temperature of both entering 
and leaving water. If temperature is within range, proceed 
with the test. If temperature is outside of the operating 
range, check refrigerant pressures and compare to Tables 
11 through 12. Verify correct water fl ow by comparing 
unit pressure drop across the heat exchanger versus the 
data in Tables 9a through 9b. Heat of extraction (HE) can 
be calculated and compared to submittal data capacity 
pages. The formula for HE for systems with water is as 
follows: 
HE = TD x GPM x 500, where TD is the temperature 
difference between the entering and leaving water, 
and GPM is the fl ow rate in U.S. GPM, determined by 
comparing the pressure drop across the heat exchanger to 
Tables 9a through 9b.
e. 
  Check air temperature rise across the air coil when 
compressor is operating. Air temperature rise should be 
between 20°F and 30°F [11°C and 17°C]. 
f.  Check for vibration, noise, and water leaks.
7.  If unit fails to operate, perform troubleshooting analysis 
(see troubleshooting section). If the check described fails 
to reveal the problem and the unit still does not operate, 
contact a trained service technician to insure proper 
diagnosis and repair of the equipment.
8.  When testing is complete, set system to maintain desired 
comfort level.
9.  BE CERTAIN TO FILL OUT AND RETURN ALL WARRANTY 
REGISTRATION PAPERWORK.
Note: If performance during any mode appears abnormal, refer 
to the CXM section or troubleshooting section of this manual. 
To obtain maximum performance, the air coil should be cleaned 
before start-up. A 10% solution of dishwasher detergent and 
water is recommended.
 WARNING! 
 CAUTION! 
WARNING! When the disconnect switch is closed, high 
voltage is present in some areas of the electrical panel. 
Exercise caution when working with energized equipment.
CAUTION! Verify that ALL water control valves are open 
and allow water fl ow prior to engaging the compressor. 
Freezing of the coax or water lines can permanently 
damage the heat pump.










