Quick Start Manual
13
Installation, Operation & Maintenance  HTV/HTD/HTH SERIES  Heat Controller, Inc.
Table 2: Antifreeze Percentages by Volume
Ground-Loop Heat Pump Applications
GROUND-WATER HEAT PUMP APPLICATIONS
Open Loop - Ground Water Systems
Typical open loop piping is shown in Figure 13. Shut off valves 
should be included for ease of servicing. Boiler drains or other 
valves should be “tee’d” into the lines to allow acid fl ushing of the 
heat exchanger. Shut off valves should be positioned to allow fl ow 
through the coax via the boiler drains without allowing fl ow into the 
piping system. P/T plugs should be used so that pressure drop 
and temperature can be measured. Piping materials should be 
limited to copper or PVC SCH80. Note: Due to the pressure and 
temperature extremes, PVC SCH40 is not recommended.
Water quantity should be plentiful and of good quality. Consult 
table 3 for water quality guidelines. The unit can be ordered with 
either a copper or cupro-nickel water heat exchanger. Consult 
table 3 for recommendations. Copper is recommended for 
closed loop systems and open loop ground water systems that 
are not high in mineral content or corrosiveness. In conditions 
anticipating heavy scale formation or in brackish water, a cupro-
nickel heat exchanger is recommended. In ground water situations 
where scaling could be heavy or where biological growth such 
as iron bacteria will be present, an open loop system is not 
recommended. Heat exchanger coils may over time lose heat 
exchange capabilities due to build up of mineral deposits. Heat 
exchangers must only be serviced by a qualifi ed technician, as 
acid and special pumping equipment is required. Desuperheater 
coils can likewise become scaled and possibly plugged. In areas 
with extremely hard water, the owner should be informed that the 
heat exchanger may require occasional acid fl ushing. In some 
cases, the desuperheater option should not be recommended due 
to hard water conditions and additional maintenance required.
Water Quality Standards
Table 3 should be consulted for water quality requirements. 
Scaling potential should be assessed using the pH/Calcium 
hardness method. If the pH <7.5 and the Calcium hardness is 
less than 100 ppm, scaling potential is low. If this method yields 
numbers out of range of those listed, the Ryznar Stability and 
Langelier Saturation indecies should be calculated. Use the 
appropriate scaling surface temperature for the application, 
150°F [66°C] for direct use (well water/open loop) and DHW 
(desuperheater); 90°F [32°F] for indirect use. A monitoring plan 
should be implemented in these probable scaling situations. Other 
water quality issues such as iron fouling, corrosion prevention and 
erosion and clogging should be referenced in Table 3.
Pressure Tank and Pump
Use a closed, bladder-type pressure tank to minimize mineral 
formation due to air exposure. The pressure tank should be 
sized to provide at least one minute continuous run time of the 
pump using its drawdown capacity rating to prevent pump short 
cycling. Discharge water from the unit is not contaminated in any 
manner and can be disposed of in various ways, depending on 
local building codes (e.g. recharge well, storm sewer, drain fi eld, 
adjacent stream or pond, etc.). Most local codes forbid the use 
of sanitary sewer for disposal. Consult your local building and 
zoning department to assure compliance in your area. 
The pump should be sized to handle the home’s domestic water 
load (typically 5-9 gpm [23-41 l/m]) plus the fl ow rate required 
for the heat pump. Pump sizing and expansion tank must be 
chosen as complimentary items. For example, an expansion 
tank that is too small can causing premature pump failure due 
to short cycling. Variable speed pumping applications should be 
considered for the inherent energy savings and smaller pressure 
tank requirements.
Water Control Valve
Note the placement of the water control valve in fi gure 13. Always 
maintain water pressure in the heat exchanger by placing the 
water control valve(s) on the discharge line to prevent mineral 
precipitation during the off-cycle. Pilot operated slow closing 
valves are recommended to reduce water hammer. If water 
hammer persists, a mini-expansion tank can be mounted on the 
piping to help absorb the excess hammer shock. Insure that the 
total ‘VA’ draw of the valve can be supplied by the unit transformer. 
For instance, a slow closing valve can draw up to 35VA. This 
can overload smaller 40 or 50 VA transformers depending on the 
other controls in the circuit. A typical pilot operated solenoid valve 
draws approximately 15VA (see Figure 22). Note the special wiring 
diagrams for slow closing valves (Figures 23 & 24).
Flow Regulation
Flow regulation can be accomplished by two methods. One method 
of fl ow regulation involves simply adjusting the ball valve or water 
control valve on the discharge line. Measure the pressure drop 
through the unit heat exchanger, and determine fl ow rate from 
tables 9a through 9c. Since the pressure is constantly varying, two 
pressure gauges may be needed. Adjust the valve until the desired 
fl ow of 1.5 to 2 gpm per ton [2.0 to 2.6 l/m per kW] is achieved. 
A second method of fl ow control requires a fl ow control device 
Type
Minimum Temperature 
for Low Temperature Protection
10°F 
[-12.2°C]
15°F 
[-9.4°C]
20°F 
[-6.7°C]
25°F 
[-3.9°C]
Methanol
Propylene Glycol
Ethanol*
21%
29%
23%
17%
24%
20%
13%
18%
16%
8%
12%
11%
* Must not be denatured with any petroleum based product










