Quick Start Manual
7
Heat Controller    DVC/DVH Inverter Mini-Split
Model R L H Hole Diameter
DVC/DVH24
(6.4in) 
163mm
(11.5in)
293mm
(1.8in)
45mm
02.56 in 
(65mm)
Fig. 8
Indoor unit installation 
1. Wall Bracket Mounting
A. There are two tabs on the back of the 
indoor unit that hold the wall bracket onto 
the unit. Press them down with a at head 
screwdriver to release the wall bracket from 
the back of the unit.
B. Mount the wall bracket ush on structural parts 
(studs) of the wall with proper unit clearances 
in consideration. (Fig. 1 and Fig. 9)
  NOTE: Any space between the unit and the 
wall may cause noise or vibration.
C. Screw the wall bracket onto the wall with 
type “A” self-tapping screws. If the wall 
is made of brick, concrete or the like, drill 
1/4” (5mm) diameter pilot holes in the wall. 
Use anchors in conjunction with mounting 
screws. 
NOTE:
• Drill holes in the wall according to the stud 
locations and corresponding mounting points 
on the actual wall bracket that comes with your 
unit. Wall brackets may vary by model and 
specications are subject to change.
• It is important to use all screws provided to 
seure the wall bracket to the wall.
2. Create Opening for refrigerant and 
condensate lines
A. Determine hole position according to the 
wall bracket that comes with your unit, the 
unit’s required clearances (Fig. 1) and which 
direction (left/right) the lines will be routed 
from the back of your unit (Fig. 14). Drill 
2.5”(65mm) hole angled downward (approx. 
45°) toward the outdoors. (Fig. 11).
  NOTE: Ensure that neither studs nor plumbing 
are located directly behine the propsed hole 
location.
B. Always use a conduit to route the piping 
though the hole in the wall. Properly seal 
the hole after routing the pipes through to 
prevent debris, insects, or small animals 
from entering.
3. Condensate Drainage
A. Run the drain hose sloping downward. Do not 
install the drain hose as illustrated in Fig.12.
B. When extending the drain hose, with locally 
purchased hose, insulate the connection 
with armaex or similar pipe insulation 
material. (Fig. 13)
Fig. 10 
Fig. 9
Wall Bracket should be
ush with the interior wall 
Fig. 12 
Fig. 11
45°
Model R L H Hole Diameter
DVC/DVH09 (3.6in) 92 (6.7in)
170mm
(1.8in)
45mm
02.56 in 
(65mm)
DVC/DVH12 (3.7in) 95mm
DVC/DVH18
(3.1in) 80mm
(3.9in)
100mm
(1.8in)
45mm
Fig. 13
Indoor
Outdoor
Wall
Wall Cap
Extension drain-
hose
Wall
Drain hose
Pipe Insulation
Do not block water ow by a rise
Do not put the end of
drain hose into water