Quick Start Manual
11
Heat Controller    DVC/DVH Inverter Mini-Split
Leak Test, Evacuation & Release of Refrigerant
The condensing unit is supplied with a R-410a 
factory approximately 25 ft. (7.6m) of line charge, 
sufcient for most matching evaporator units. 
Charge must be added for interconnecting tubing. 
See Field Charging Section of this manual.
The unit’s service valves are shipped in the closed 
position and should not be opened until nal 
connections and evacuation are completed. 
WARNING
It is illegal to discharge refrigerant into the 
atmosphere. Use proper reclaiming methods 
and equipment when working on the refrigerant 
containing parts of the unit. Service should be 
performed by a QUALIFIED service agency and 
certied technicians.
Electrical Precautions
1. Refer to the unit’s rating plate for power supply voltage. Ensure adequate electrical supply 
is available.
2. Ensure the air conditioner is properly grounded.
3. Connect wiring to the unit according to the electrical diagram located on the unit.
4. All wiring must comply with local and national electrical codes and be installed by a quali-
ed electrician.
5. An individual branch circuit must be available.
6. Properly size the HACR breaker/fuse based on nameplate date.
7. Improper connections and inadequate grounding can cause injury or death.
8. Connect all wiring tightly. Loose wiring may cause overheating at connection points and 
create a possible re hazard.
9. Match terminal strip numbers/labels and colors between indoor and outdoor wiring. Errone-
ous wiring may cause re/shock.
10. Always use strain reliefs and outdoor cable cover to protect wiring.
CAUTION
The recommended procedure for leak test, evacuation, 
and release of refrigerant is outlined below:
1. Complete the nal piping connections to the indoor 
and outdoor units using high temperature brazing 
alloy.
2. Connect a charging manifold to the service ports 
provided at the service valves.
3. Pressurize the lines and evaporator with nitrogen 
and leak check all connections with soap bubbles. 
Repair as necessary any faulty joints. If brazing is 
required be sure to RELEASE THE NITROGEN 
FIRST. Re-test as needed.
4. Connect a vacuum pump to the manifold center 
connection, start the pump and open the manifold 
valves.
5. Evacuate to 500 microns or less for a minimum of 
30 minutes. Close the manifold valves and shut off 
the pump. Note the vacuum reading and wait 15 
minutes. Take a new vacuum reading. A reading 
of 800 microns or higher indicates the presence of 
moisture or a leak.
6. Repair as necessary and repeat steps 3, 4 & 5.
7. Conrm that manifold valves are closed and 
disconnect the vacuum pump.
8. Remove the caps from the services valves. Open 
the valves to the fully ‘back-seat’ position. Replace 
service valve caps and tighten.










