User manual

15Hearth & Home Technologies • BE-36-C, BE-36-CIPI • 397-981 Rev. V 1/07
Figure 5.6
1. Top Vent - Horizontal Termination - (continued)
Three Elbows
H
2
V
2
H
1
V
1
NOTE: There MUST be a 25%
reduction in total H when using
ex vent except when using the
simple up and out installation
(see Figure 5.3).
Note: Use SL D- Series
components only.
V Minimum
H
1
Maximum H
1
+ H
2
Maximum
BE-36-C NG & LP BE-36-C NG BE-36-C LP
90 Elbow Only 1-1/2 ft. 457 mm 2 ft. 610 mm 2 ft. 610 mm
1/2 ft. 152 mm 1-1/2 ft. 457 mm 4 ft. 1.2 m 3 ft. 914 mm
1-1/2 ft. 457 mm 3 ft. 914 mm 6 ft. 1.8 m 6 ft. 1.8 m
2-1/2 ft. 762 mm 5 ft. 1.5 m 10 ft. 3.0 m 10 ft. 3.0 m
3-1/2 ft. 1.1 m 7 ft. 2.1 m 14 ft. 4.3 m 14 ft. 4.3 m
4-1/2 ft. 1.4 m 15 ft. 4.6 m 14 ft. 4.3 m 14 ft. 4.3 m
H
1
+ H
2
MAX. =14 FT (4.3 m)
V
1
+ V
2
+ H
1
+ H
2
MAX. = 40 FT (12.2 m)