Stove User Manual
Page 11
Isle Royale Wood Stove
R
250-5763E
November 22, 2011
CANADA
203mm (8")
203mm
(8")
203mm
(8")
457mm (18")
1219mm
(48")
Minimum
1137mm (44-3/4")
Minimum
16" from glass - std legs
8"
USA
Fuel loading door
36-3/4"
Minimum
39-1/4"
Minimum
must extend
length of flue and
2" (51mm)
beyond each
side of pipe
USA - Required
CANADA - Recommended
16"
optional coverage
optional
coverage
optional
coverage
8”
36-9/16"
required coverage
38-5/8"
51"
30-3/8"
51"
USA Installations
fuel loading door
A. Hearth Protection Requirements
FLOOR PROTECTION: Floor protector must be non-
combustible material, extending beneath heater and to the
front, sides and rear as indicated. The fl oor must be non-
combustible or otherwise adequately protected from radiant
heat given off by the unit and from sparks and falling embers.
A layer of thin brick or ceramic tile over a combustible fl oor
is not suffi cient.
In US installations, i
t is necessary to install a fl oor protec-
tor a minimum of 16
inches (406mm) in front of glass and 8
inches (203mm) to both sides of the fuel loading door. Open
the door and measure 8 inches (203mm) from the side edge
of the opening in the face of the appliance. *See exception.
In Canada, similar fl oor protection must be provided 18
inches (457mm) in front and 8 inches (203mm) from the
sides and rear of the stove. *See exception.
*EXCEPTION: Non-combustible fl oor protections must
extend beneath the fl ue pipe when installed with horizontal
venting and extend 2 inches (51mm) beyond each side.
See Figure 11.4.
4
Installation Considerations
WARNING
Fire Risk.
• Hearth pads must be installed exactly as
specified.
High temperatures or hot embers may ignite
concealed combustibles.
Figure 11.1 Figure 11.2
Figure 11.3
Figure 11.4