- Herath and Home Indoor/Outdoor Gas Fireplace Installation and Operation

31Heat & Glo LifeStyle Collection • Twilight-II-B • 2108-900 Rev. M • 11/08
Figure 10.5 Exterior View
Fire Risk.
Finish all edges and fronts to clearances
and speci cations listed in manual.
Black metal columns may be covered with
non-combustible material only.
Do NOT overlap combustible materials onto appliance
front.
Install combustible materials only up to specified
clearances on top, front and side edges.
Seal joints between the nished wall and appliance top
and sides using only a 300º
F minimum sealant.
May install non-combustible materials to cover gap be-
tween facing material and appliance (see Figure 10.5).
Fire Risk.
Water Intrusion Risk.
Hood is required.
Flashing and non-combustible sheathing must be
installed before facing materials.
Facing must be non-combustible and seal tight to
replace front.
Risk of Fire
Non-combustible clearances must be
maintained.
Sheetrock, wood or other combustibles must NOT
be used as sheathing or facing in the non-
combustible zone.
• See Sections 3 & 8 for proper clearances.
• See Section 1 for combustible/non-
combustible de nitions.
2-3/4 in.
12 in.
HOOD
NON-COMBUSTIBLE
SHEATING
6 in.
MAX.
NON-COMBUSTIBLE
FACING
THERE MUST BE NO GAP
BETWEEN BRICK LEDGE,
FACING MATERIAL AND
APPLIANCE FRONT.
6 in. MAXMUM PROJECTION
FROM FACE OF FIREPLACE
BRICK LEDGE
NON-COMBUSTIBLE
SHEATHING
(SUPPLIED)
COMBUSTIBLE
SHEATHING
HOUSEWRAP
REQUIRED
FLASHING
(SUPPLIED)
HOUSE
WRAP