Specification Sheet
model TWBS.SHE
AXION
®
Thermostatic Mixing Valves
FEATURES & BENEFITS
SPECIFICATIONS
BYPASS
Best-in-class cold water bypass ow (68% of rated
tempered water ow) means continued protection
under adverse conditions.
POSITIVE SHUT OFF
Actively suspends hot water ow when cold water supply
is lost to protect against scalding.
PRESSURE DROP
Lowest internal pressure drop for this valve class –
essential where supply pressure is low.
OPERATING RANGE
Minimal outlet temperature variation is achieved by
having the best minimum ow rate in the industry.
SHUTTLE DESIGN
Superior shuttle design combined with premium
material selection eliminates valve binding and reduces
maintenance costs.
MIXING CHAMBER
Innovative funnel design generates turbulent ow to
ensure consistent temperature blending across entire
ow range.
LEAD FREE
Certied to NSF61 and California Health and Safety Code
116875 (AB 1953-2006).
FLOW RATES
Flow range of 1 to 74 gpm (280 L) provides service for
multiple emergency combination showers or multiple
eyewashes to reduce hardware costs.
ANTI-SCALD PROTECTION
Redundant anti-scald protection; primary protection
comes from the main tempering valve. An additional
high temperature shut-off valve provides a secondary
level of protection; the internal cold water bypass takes
over to supply cold water in the event of a hot water
pressure loss or main tempering valve failure.
MEDICALLY SUPERIOR RESPONSE
AXION’s superior design and technology provide a complete
safety solution for increased victim comfort.
EXTENDED WARRANTY
3-year extended warranty based on superior engineering
and best-in-class material selection means reliable
protection you can trust for the long term.
FLOW CAPACITIES
MODEL
TWBS.SHE
INLET
1-1/4”
50
189
1
4
5
.345
30
114
10
.689
43
163
15
1.03
52
197
20
1.38
60
227
30
2.07
74
280
45
3.10
91
344
60
4.13
105
397
PSI
BAR
GPM
L/MIN
1-1/4”
OUTLET
MINIMUM
FLOW
PRESSURE DROP
INTERNAL COLD
WATER BY-PASS
AT 30PSI DROP
1455 Kleppe Lane :: Sparks, NV 89431 :: p. 775.359.4712 :: f. 775.359.7424 :: e. info@hawsco.com :: www.hawsco.com :: 21 November, 2013
DISCLAIMER: Continued product improvements make specications subject to change without notice. Check www.hawsco.com for the latest product information and updates.
MINIMUM MAXIMUM
Flow Rate 74 GPM 280 LPM 1 GPM 4 LPM
Hot Inlet Temperature 180° F 82° C 120° F 49° C
Recommended Hot
Inlet Temperature 140° F 60° C
Cold Inlet Temperature 70° F 21° C 40° F 4° C
Adjustable Outlet
Temperature Range 85° F 29° C 60° F 16° C
Operating Pressure 125 PSI 8.6 BAR
Factory Temperature
Set Point 85° F 29° C
Cold Water Bypass 50 GPM 189 LPM @ 30 PSI
Inlet Ports: 1-1/4” NPT(f) Outlet Port: 1-1/4” NPT(F)
Maximum Inlet Pressure Differential: +/- 10%
Listings: ASSE 1071, CSA B125.3, NSF/ANSI 61-section 8,
NSF/ANSI 372, California Health and Safety Code
116875 (AB 1953-2006).