Specification Sheet
model 92 01H
AXION
®
Thermostatic Mixing Valves
FEATURES & BENEFITS
SPECIFICATIONS
BYPASS
Best-in-class cold water bypass ow (65% of rated
tempered water ow) means continued protection
under adverse conditions.
POSITIVE SHUT OFF
Actively suspends hot water ow when cold water supply
is lost to protect against scalding.
PRESSURE DROP
Lowest internal pressure drop for this valve class –
essential where supply pressure is low.
TEMPERATURE MANAGEMENT
Parafn-based thermal actuation technology keeps
outlet temperature within tight specications to prevent
scalding and hypothermia.
SHUTTLE DESIGN
Superior shuttle design combined with premium
material selection eliminates valve binding and reduces
maintenance costs.
MIXING CHAMBER
Innovative funnel design generates turbulent ow to
ensure consistent temperature blending across entire
ow range.
DEPOSITS RESISTANT
Lime and calcium resistant materials used throughout
prevent valve sticking and provide a long service life.
FLOW RATES
Flow range of 1 to 31 GPM (117.3 L) provides service
for one emergency combination shower or multiple
eyewashes, reducing complexity and hardware costs.
LEAD FREE
Certied to NSF61 and California Health and Safety Code
116875 (AB 1953-2006).
ANTI-SCALD PROTECTION
Redundant anti-scald protection with internal cold water
bypass ensures reliable protection. Main tempering valve
provides primary protection while backup shutoff valve
provides secondary high-temp protection. Internal cold
water bypass supplies cold water if hot water supply or
main tempering valve fails.
MEDICALLY SUPERIOR RESPONSE
AXION’s superior design and technology provide a complete
safety solution for increased victim comfort.
EXTENDED WARRANTY
3-year extended warranty based
on superior engineering and
best-in-class material selection
means reliable protection you
can trust for the long term.
FLOW CAPACITIES
MODEL
9201H
INLET
1”
20
76
1
4
5
.345
13
49
10
.689
18
68
15
1.03
22
83
20
1.38
25
95
30
2.07
31
117
45
3.10
38
144
60
4.13
44
167
PSI
BAR
GPM
L/MIN
1-1/4”
OUTLET
MINIMUM
FLOW
PRESSURE DROP
INTERNAL COLD
WATER BY-PASS
AT 30PSI DROP
Model 9201H - Thermostatic Mixing Valve (patent pending)
MINIMUM MAXIMUM
Flow Rate 31 GPM 117.3 LPM 1 GPM 4 LPM
Hot Inlet Temperature 180° F 82° C 120° F 49° C
Recommended Hot
Inlet Temperature 140° F 60° C
Cold Inlet Temperature 70° F 21° C 40° F 4° C
Adjustable Outlet
Temperature Range 90° F 32° C 60° F 16° C
Operating Pressure 125 PSI 8.6 BAR
Factory Temperature
Set Point 85° F 29° C
Cold Water Bypass 20 GPM 75.7 LPM @ 30 PSI
Inlet Ports: 1” NPT(f) Outlet Port: 1-1/4” NPT(F)
Maximum Inlet Pressure Differential: +/- 10%
Listings: ASSE 1071, CSA B125.3 , NSF/ANSI 61-section 8,
NSF/ANSI 372, California Health and Safety Code
116875 (AB 1953-2006).
1455 Kleppe Lane :: Sparks, NV 89431 :: p. 775.359.4712 :: f. 775.359.7424 :: e. info@hawsco.com :: www.hawsco.com :: 21 November 2013
DISCLAIMER: Continued product improvements make specications subject to change without notice. Check www.hawsco.com for the latest product information and updates.