Installation Guide

APPROVED:
DRAWN:
PART NUMBER
SCALE:
SHEET OF
REVISION
DRAWING TYPE: SIZE: A
BY:ECN NO.
DATE:
DATE:
ECN:
REVISED PER
CHK'D.:
Haws Corporation - All Rights Reserved.
HAWS and other trademarks used in these materials are the exclusive property of Haws Corporation.
C
R
MODEL(S)
1455 KLEPPE LANE
SPARKS, NEVADA 89431
(775) 359-4712 FAX (775) 359-7424
E-MAIL: HAWS@HAWSCO.COM
WEBSITE: WWW.HAWSCO.COM
THIS DOCUMENT IS TRUE AND CORRECT AT TIME OF PUBLICATION. CONTINUED PRODUCT IMPROVEMENTS
MAKE SPECIFICATIONS AND MEASUREMENTS SUBJECT TO CHANGE WITHOUT NOTICE.
JL
05/12/16
2
0510000480.D
7603
SAFETY KEG EYEWASH
N/A
11
FV
10/24/16
5074
VWC
INSTALLATION
5142
2016
CC
NOTES:
1. TO COMPLY WITH ANSI/ISEA Z358.1-2014 FOR EMERGENCY EYEWASH OR EYEWASH:
- UNIT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND ACCEPTABLE
PLUMBING PRACTICES.
- EYE/FACE WASH SHALL BE POSITIONED SUCH THAT STREAMS ARE 15.3 CM (6 IN.) MINIMUM FROM WALL OR
NEAREST OBSTRUCTION.
2 DIMENSIONS MAY VARY BY ±1/2" [12.7mm].
3 EYEWASH HEAD ASSEMBLY MUST BE PARALLEL TO WALL OR OBSTRUCTION TO MEET CRITERIA STATED IN
ACCORDANCE TO NOTE 1.
4 USE DOW CORNING 832 SEALANT ON DIP TUBE THREADS; HAND TIGHTEN.
5 TIGHTEN CLAMP BOLTS TO 10 FT. LB. OF TORQUE.
6. FILL WITH 10 GALLONS OF CLEAN POTABLE WATER (NOTE FILL LINE ON MAIN LABEL); PRESSURIZE TO 75 PSI.
REFILL IF PRESSURE < 70 PSI.
WALL
15
15
16
[404mm]
39
1
2
" [1003mm]
AIR VALVE
PRESSURE
RELIEF
VALVE
PUSH FLAG
PRESSURE
GAUGE
EYEWASH
PLUMBING
GASKET
4 DIP TUBE
COTTER PIN
CLAMP
COTTER PIN
CLAMP BOLT
CLAMP BOLT
5
5
3
2
1/2" NPT (FEMALE) CONNECTION
FOR OPTIONAL EYE/FACE
& BODY HOSE UNIT

Summary of content (1 pages)