Information
12
Publication No: US-CYC-SG-003 - June 2008
www.enersys.com
Products 5 min 10 min 15 min 30 min 60 min 90 min 5 hr 8 hr 10 hr 20 hr
BC cell (2.5Ah) 118.3 72.8 54.3 32.2 19.3 14.0 4.85 3.14 2.55 1.33
DURATION
Constant current discharge/amps to 1.67Vpc @ 25°C
Products 5 min 10 min 15 min 30 min 60 min 90 min 5 hr 8 hr 10 hr 20 hr
BC cell (2.5Ah) 197.3 142.4 105.5 63.5 36.8 25.6 9.20 6.04 4.95 2.60
DURATION
Constant current discharge/watts per cell to 1.67Vpc @ 25°C
Products Cyclic Float Storage & Charge C/5 Cycle life Float life at
discharge 100% DOD 25°C (20°C)
BC cell (2.5Ah) CV 2.45-2.50 CV 2.27-2.35 -65°C to +80°C -40°C to -80°C 300 10 years
CC* CC* (15 years)
CHARGING PER CELL
TEMPERATURE RANGE LIFE EXPECTANCY
Charging/Temperature/Life:
Maximum recommended storage time before recharge - 24 months @ 25°C or 2.0Vpc, whichever is earlier
Atmospheric pressure range - Vacuum to 8 atmospheres
Mounting - Terminal torque must not exceed 35 in-lbs. (3.95 Nm)
*Users planning to use CC should consult the EnerSys
®
Application Support Department
UL Recognized Component. Meets UL 1989
Caution: Batteries contain toxic materials (Pb and H2SO4) • Avoid short circuit • Do not charge in gas-tight container
Sealed-lead rechargeable battery must be recycled or disposed of properly. Contact EnerSys
®
Customer Service for details.
CYCLON
®
Battery 12 Volt 2x3 25.0Ah Case
0820-2018
BC Double Slot, 8.05 204.5 5.45 138.4 7.25 184.2 22.86 10.4 Yes
Copper Straps
0820-0020 BC Double Slot, 8.05 204.5 5.45 138.4 7.25 184.2 22.86 10.4 No
Copper Straps
Product Length Width Height Weight Leads
Number Description in. mm in. mm in. mm lbs. kg
All dimensions, excluding weight, are maximum
CYCLON
®
Battery BC Single Cell performance specifications