Datasheet
Products 5 min 10 min 15 min 30 min 60 min 90 min 5 hr 8 hr 10 hr 20 hr
D cell (2.5Ah) 14.3 8.1 5.9 3.4 1.9 1.4 .48 .32 .26 .13
X cell (5.0Ah) 28.9 18.1 13.5 7.1 4.0 2.8 1.0 .61 .52 .26
E cell (8.0Ah) 41.7 26.4 19.0 11.0 6.2 4.4 1.6 1.0 .81 .42
DURATION
4V & 6V Constant current discharge/amps to 1.67Vpc @ 25°C
Products 5 min 10 min 15 min 30 min 60 min 90 min 5 hr 8 hr 10 hr 20 hr
D cell (2.5Ah) 25.3 15.9 11.7 6.8 3.8 2.7 .93 .60 .49 .25
X cell (5.0Ah) 48.8 32.3 24.2 13.8 7.8 5.6 2.0 1.2 1.0 .52
E cell (8.0Ah) 77.8 51.0 35.5 21.1 12.4 8.9 3.1 2.0 1.7 .85
DURATION
4V & 6V Constant power discharge/watts per cell to 1.67Vpc @ 25°C
Products Cyclic Float Storage, discharge Safety C/5 Cycle life Float life at
& charge pressure 100% DOD 25°C (20°C)
relief valve
4V D, X, & E CV 4.90-5.00 CV 4.54-4.70 -40°C to +40°C 8 psi 300 Up to 8 yrs
Monobloc CC* CC* (Up to 8 yrs)
6V D, X, & E CV 7.35-7.50 CV 6.81-7.05 -40°C to +40°C 8 psi 300 Up to 8 yrs
Monobloc CC* CC* (Up to 8 yrs)
CHARGING PER CELL
TEMPERATURE RANGE LIFE EXPECTANCY
Maximum recommended storage time before recharge - 24 months @ 25°C or 2.0Vpc, whichever is earlier
Atmospheric pressure range - Vacuum to 2 atmospheres
Mounting - Each Monobloc is equipped with mounting holes in the cover. The tightening torque for mounting the Monobloc is 25 in-lbs. When using 4 mounting bolts, small spacers
(washers) 1 to 3 mm thick should be placed between the battery and the mounting surface to prevent bowing or stressing the battery case.
*Users planning to use CC should consult the EnerSys
®
Application Support Department.
UL Recognised Component. Meets UL 1989
Caution: Batteries contain toxic materials (Pb and H2SO4) • Avoid short circuit • Do not charge in gas-tight container
Sealed-lead rechargeable battery must be recycled or disposed of properly. Contact EnerSys
®
Customer Service for details.
Charging/Temperature/Life
CYCLON
®
Battery 4V/6V Monobloc performance specifications
15
Publication No: EN-CYC-SG-003 - December 2008
www.enersys-emea.com