Instruction Manual

Form No. EBOOSTERM-0321
7
English
SPECIFICATIONS
Circuit Breaker and Fused Disconnect Switch Sizes — 4 to 12 kW
The shaded area contains electrical information for International models only.
NOTE: 250 kcmil maximum wire size for terminal block.
kW Volts Phase
Amp Draw Breaker or
Fuse
Size
Copper Wire
Size Conduit SizeL1 L2 L3
4 208 1 19 19 -- 30 10 1/2
240 1 17 17 -- 30 10 1/2
480 1 8 8 -- 15 14 1/2
5 208 1 24 24 -- 30 10 1/2
240 1 21 21 -- 30 10 1/2
480 1 10 10 -- 15 14 1/2
6 208 1 29 29 -- 40 8 1/2
208 3 14 25 14 40 8 1/2
240 1 25 25 -- 40 8 1/2
240 3 13 22 13 30 10 1/2
380 3 9.2 9.2 9.2 15 14 1/2
480 3 6 11 6 15 14 1/2
600 3 5.7 5.7 5.7 15 14 1/2
7 208 1 34 34 -- 50 8 1/2
208 3 17 29 17 40 8 3/4
240 1 29 29 -- 40 8 1/2
240 3 15 25 15 40 8 1/2
380 3 11.4 11.4 11.4 15 14 1/2
480 3 7 13 7 20 12 1/2
600 3 6.7 6.7 6.7 15 14 1/2
9 208 1 43 43 -- 60 6 1/2
208 3 22 38 22 50 8 1/2
240 1 38 38 -- 50 8 1/2
240 3 19 33 19 50 8 1/2
380 3 13.3 13.3 13.3 20 12 1/2
480 3 9 16.3 9 30 12 1/2
600 3 8.7 8.7 8.7 15 14 1/2
9.9 208 1 47.5 47.5 -- 60 6 1/2
208 3 27.5 27.5 27.5 40 8 1/2
10.4 208 3 28.8 28.8 28.8 40 8 1/2
10.5 208 1 51 51 -- 70 4 3/4
208 3 29 29 29 40 8 1/2
240 1 44 44 -- 60 6 1/2
240 3 25.3 25.3 25.3 40 8 1/2
480 3 12.6 12.6 12.6 20 12 1/2
600 3 10 10 10 15 14 1/2
11.4 240 1 47.5 47.5 -- 60 6 1/2
240 3 27.5 27.5 27.5 40 8 1/2
480 3 13.7 13.7 13.7 20 12 1/2
12 208 1 58 58 -- 90 3 1
208 3 33 33 33 50 8 1/2
240 1 50 50 -- 70 4 3/4
240 3 29 29 29 40 8 1/2
380 3 19.1 19.1 19.1 30 10 1/2
480 3 14.5 14.5 14.5 20 12 1/2
600 3 11.6 11.6 11.6 15 14 1/2