Product Overview
CONTACTORS
Line Voltage
Full Load Amps
Resistive Amps
@ 600 VAC
Locked Rotor Amps
@ 240/277 VAC
Locked Rotor Amps
@ 480 VAC
Locked Rotor Amps
@ 600 VAC
3 Pole Contactors
50 65 300 250 200
60 75 360 300 240
75 90 450 375 300
90 120 540 450 360
120 150 720 600 480
Horsepower Rating
Full Load
Amps
120 V 240 V 480 V 600 V
Single Phase Three Phase Single Phase Three Phase Single Phase Three Phase Single Phase Three Phase
3 Pole Contactors
50 3 – 10 15 – 30 – 30
60 5 – 10 25 – 30 – 30
75 5 – 15 25 – 40 – 40
90 7.5 – 20 30 – 50 – 50
120 7.5 – 20 30 – 50 – 50
Standard Fault Short Circuit Rating
Suitable for use on a circuit capable of delivering not more than 5k rms symmetrical amperes,
600 Volts maximum at 400% of fuse and circuit breaker.
High Fault Short Circuit Rating
Suitable for use on a circuit capable of delivering not more than 100k rms symmetrical amperes as shown.
Maximum Circuit Breaker Maximum J Fuse
480 Volts Maximum Minimum Enclosure Volume 600 Volts Maximum Minimum Enclosure Volume
05 150 A 256 cu. in. 200 A 256 cu. in.
06 150 A 256 cu. in. 200 A 256 cu. in.
07 225 A 1008 cu. in. 200 A 1008 cu. in.
09 225 A 1008 cu. in. 200 A 1008 cu. in.
12 225 A 1008 cu. in. 200 A 1008 cu. in.
Note: for a circuit capable of delivering more than 5k rms symmetrical amperes, the equipment enclosure must have a minimum of four
fastening points or a piano hinge and two fastening points.
3 Pole Contactor 50–120 FLA
HCD Series
©2017 Hartland Controls | Printed in USA | All rights reserved | PS0100610171000
Multiple mounting and termination options available, contact us for more information.