Product Overview
CONTACTORS
Line Voltage
Full Load Amps
Resistive Amps
@ 600 VAC
Locked Rotor Amps
@ 240/277 VAC
Locked Rotor Amps
@ 480 VAC
Locked Rotor Amps
@ 600 VAC
3 Pole Contactors
20 30 120 100 80
25 35 150 125 100
30 40 180 150 120
40 50 240 200 160
4 Pole Contactors
20 30 120 100 80
25 35 150 125 100
30 40 180 150 120
40 50 240 200 160
Horsepower Rating
Full Load
Amps
120 V 240 V 480 V 600 V
Single Phase Three Phase Single Phase Three Phase Single Phase Three Phase Single Phase Three Phase
3 Pole Contactors
20 1.5 – 3 7.5 – 7.5 – 7.5
25 2 – 5 7.5 – 15 – 20
30 2 – 5 10 – 15 – 20
40 3 – 7.5 10 – 20 – 25
4 Pole Contactors
30 1.5 – 3 7.5 – 7.5 – 7.5
40 2 – 5 10 – 15 – 20
Standard Fault Short Circuit Rating
Suitable for use on a circuit capable of delivering not more than 5k rms symmetrical amperes,
600 Volts maximum at 400% of fuse and circuit breaker.
High Fault Short Circuit Rating
Suitable for use on a circuit capable of delivering not more than 100k rms symmetrical amperes as shown.
Maximum Circuit Breaker Any Listed Fuse (except as noted)
480 Volts Maximum Minimum Enclosure Volume 600 Volts Maximum Minimum Enclosure Volume
00, 40 80 A 144 cu. in. 60 A
96 cu. in. (1 & 2 Pole)
144 cu. in. (3 & 4 Pole)
01, 41 80 A 144 cu. in. 60 A
02, 42 80 A 144 cu. in. 60 A
04, 44 100 A 144 cu. in.
100 A max.
Class J Fuse (1 & 2 Pole)
100 A (3 & 4 Pole)
Note: for a circuit capable of delivering more than 5k rms symmetrical amperes, the equipment enclosure must have a minimum of four
fastening points or a piano hinge and two fastening points.
3 & 4 Pole Contactor 20–40 FLA
HCC Series