Datasheet
Han-Kit
®
Page 6
Han
®
4 A Metal Version
Part-Number
10 20 004 0001
10 20 004 0003
Dimensions in mm
Han-Kit
®
-4AGM
Hood Han
®
3 A straight
Bulkhead mounted hous.
1)
Han
®
3 A straight
Material Die cast zinc alloy
Protection degree
2)
IP 67
Cable gland M20, metal
Cable diameter 5 - 9 mm / 6 - 12 mm
Insert Han
®
4 A, 4-pins + PE
Screw terminal 1-2.5 mm², AWG 18-14
Electrical data accd. to DIN EN 61 984
3)
10 A 230/400 V 4kV 3
Rated current
Rated voltage
conductor-ground
Rated voltage
conductor-conductor
Rated impulse voltage
Pollution degree
Rated voltage
accd. to UL/CSA 600 V
Han-Kit
®
-4AWM
Hood Han
®
3 A straight
Bulkhead mounted hous.
1)
Han
®
3 A angled
Material Die cast zinc alloy
Protection degree
2)
IP 67
Cable gland M20, metal
Cable diameter 5 - 9 mm / 6 - 12 mm
Insert Han
®
4 A, 4-pins + PE
Screw terminal 1-2.5 mm², AWG 18-14
Electrical data accd. to DIN EN 61 984
3)
10 A 230/400 V 4kV 3
Rated current
Rated voltage
conductor-ground
Rated voltage
conductor-conductor
Rated impulse voltage
Pollution degree
Rated voltage
accd. to UL/CSA 600 V
Han-Kit
®
-4AWSM
Hood Han
®
3 A angled
Bulkhead mounted hous.
1)
Han
®
3 A straight
Material Die cast zinc alloy
Protection degree
2)
IP 67
Cable gland M20, metal
Cable diameter 5 - 9 mm / 6 - 12 mm
Insert Han
®
4 A, 4-pins + PE
Screw terminal 1-2.5 mm², AWG 18-14
Electrical data accd. to DIN EN 61 984
3)
10 A 230/400 V 4kV 3
Rated current
Rated voltage
conductor-ground
Rated voltage
conductor-conductor
Rated impulse voltage
Pollution degree
Rated voltage
accd. to UL/CSA 600 V
10 20 004 0005
Assembly cut out
bulkhead mounted
housing
22 x 22 mm
Assembly cut out
bulkhead mounted
housing
22 x 22 mm
1) Bulkhead mounted housing
with ange gasket
2) Protection degree acc. to DIN
EN 60 529 in locked position
3) For only use in grounded
circuits
Assembly cut out
bulkhead mounted
housing
22 x 22 mm