Brochure

L Series (Page 40-42)
NOTES:
1. Table 1 based on up to 4-foot grille length. For longer lengths, correct
throw and NC per Table 2.
2. When using continuous grille lengths with alternate active and inactive
sections, a reduction in throw can be obtained by omitting the factors
contained in Table 2.
3. Bar style 30 and 0
Increase Table 1 NC + 5 NC
4. Supply air temperature effect on horizontal throw is shown in Table 3.
vertical down-throw at varying supply temperatures is shown in Table 4.
5. When spreading the air path with a horizontal deflection of 22º per side in
grille lengths up to 4 feet:
Multiply Table 1 Throw x .75
Increase Table 1 NC + 5 NC
Multiply Table 1 P
s
x 1.20
Multiply Table 5 A
k
x .90
6. Terminal velocities (V
t
) at the minimum and maximum throw (T) values
are rated at 125 FPM and 75 FPM respectively with corresponding room
velocities (V
r
) of 50 FPM and 35 FPM.
Sidewall Sill/Floor
00 and 15 30 and 01 00 and 15 30 and 01 Min.-Max. Min.-Max. @ -18F T @ -25F T
20 1 .01 .01 500 575 6-9 1-2 8 9 <20
1 .03 .04 750 865 7-10 2-3 25
2 .01 .01 475 545 6-9 1-2 20
1 .05 .07 1000 1150 9-13 3-5 30
2 .02 .03 635 730 8-11 2-4 25
2 .01 .01 460 530 7-10 2-3 20
1 .03 .12 1250 1440 11-16 4-9 30
2 .03 .04 790 910 10-14 3-7 25
2 .02 .03 575 660 9-13 2-6 20
3 <.01 .01 440 505 8-12 2-5 <20
2 .05 .07 950 1090 12-18 5-11 30
2 .02 .03 690 795 11-16 4-9 25
3 .01 .01 530 610 10-14 3-7 20
4 <.01 .01 370 425 8-12 2-5 <20
2 .06 .08 1110 1275 14-20 7-13 30
2 .03 .04 810 935 13-19 6-12 30
3 .02 .03 660 760 11-16 4-9 25
4 <.01 .01 435 500 10-14 3-7 <20
2 .08 .10 1275 1450 16-23 9-16 30
2 .04 .05 920 1060 15-21 8-14 30
3 .03 .04 700 805 13-18 6-11 25
4 .01 .01 495 570 11-16 4-9 20
2 .05 .07 1030 1185 17-24 10-17 30
3 .04 .05 785 905 15-21 8-14 30
4 .01 .02 550 635 13-18 6-11 25
5 <.01 .01 450 520 11-16 4-9 20
2 .06 .08 1150 1325 19-27 12-20 30
3 .04 .05 875 1010 16-23 9-16 30
4 .02 .03 620 715 14-20 7-13 25
5 .01 .01 500 575 12-18 5-11 20
3 .06 .08 1050 1210 19-28 11-20 30
4 .03 .04 745 855 17-24 9-16 30
5 .02 .03 600 680 15-22 7-14 25
6 <.01 .01 480 550 13-19 5-11 20
3 .08 .11 1220 1410 22-32 14-24 35
4 .04 .05 870 1000 19-28 11-20 30
5 .02 .03 700 810 17-25 9-17 25
6 .01 .01 560 645 15-22 7-14 20
4 .05 .07 990 1140 22-32 13-23 35
5 .03 .04 800 925 19-29 10-20 30
6 .02 .03 640 735 18-26 9-17 25
8 .01 .01 460 530 15-22 6-13 20
4 .07 .09 1110 1275 25-36 16-27 35
5 .04 .05 900 1035 22-33 13-24 30
6 .03 .04 725 835 20-30 11-21 25
8 .02 .03 520 600 17-25 8-16 20
4 .08 .11 1240 1425 28-41 - 40
5 .05 .07 1000 1150 24-36 - 35
6 .04 .05 800 925 23-33 - 30
8 .02 .03 575 665 20-28 - 25
5 .08 .11 1250 1440 30-46 - 40
6 .05 .07 1000 1150 27-39 - 35
8 .03 .04 720 830 25-35 - 30
10 .01 .01 550 625 21-32 - 25
6 .07 .09 1200 1375 33-48 - 40
8 .04 .05 865 1000 29-42 - 35
10 .02 .03 665 765 25-39 - 30
12 .01 .01 545 630 23-33 - 25
8 .05 .08 1020 1175 34-48 - 40
10 .03 .04 780 900 29-45 - 35
12 .02 .03 640 735 26-38 - 30
8 .08 .11 1170 1350 40-55 - 45
10 .04 .05 890 1025 33-50 - 40
12 .03 .04 730 845 33-44 - 35
50
40
30
Throw (T) in Feet
Minimum Ceiling
Height in Feet
9
11
Table 1 - Supply Air
Min. P
s
in H
2
0
Bar Style
CFM/Ft of
total
Linear
length
Listed
Width
in
Inches
NC
9
10
60
9
12
9
11
Face Velocity (V
k
) FPM
Bar Style
70
10
12
80
10
12
90
11
13
100
11
13
120
11
13
140
11
14
160
12
15
180
12
15
200
12
15
250
13
15
400
14
16
300
13
15
350
13
15
Symbols:
V
t
Terminal Velocity in FPM
V
r
Room Velocity in FPM
V
k
Face Velocity in FPM
A
k
Outlet Area in Square Feet
A
n
Neck Area in Square Feet
P
s
Static Pressure in H2O
NC 18dB Room Attenuation
T Throw in Feet: see Note 6.
∆T Temperature Differential
Recommended Noise Criteria and Face Velocity Ranges are on page 75
100
Engineering Data
Engineering Data