Brochure
S Series (Page 43-47)
Type 75 (" " Slot)
Ceiling Sidewall Sill
Min.-Max. Min.-Max. Min.-Max. @ -18F T @ -25F T
10 1 .01 335 4-6 2-4 1-2 7 9 <20
1 .04 670 8-11 6-9 2-3 20
2 <.01 400 6-9 4-7 1-2 <20
1 .09 1000 10-14 8-12 3-4 25
2 .02 600 8-11 6-9 2-3 20
3 <.01 430 7-9 5-7 1-2 <20
1 .16 1340 13-17 11-15 4-6 30
2 .04 800 10-14 8-12 3-4 25
3 .02 575 9-12 7-10 2-3 20
4 .01 445 8-11 6-9 2-3 <20
2 .06 1000 11-15 9-13 4-6 25
3 .03 715 10-14 8-12 3-4 20
4 .02 555 9-13 7-11 2-4 <20
5 <.01 415 7-12 6-10 2-3 <20
2 .09 1200 13-17 11-15 5-8 30
3 .04 860 12-16 10-14 4-7 25
4 .02 665 11-15 9-13 3-6 20
5 .01 500 9-13 7-11 3-4 <20
2 .13 1400 15-20 13-18 6-11 30
3 .06 1000 13-18 11-16 5-9 25
4 .03 775 12-16 10-14 4-7 20
5 .02 585 10-15 8-13 3-5 <20
6 .01 500 9-14 7-12 2-5 <20
3 .07 1140 14-20 12-18 6-11 30
4 .04 885 13-19 11-17 5-10 25
5 .03 665 13-17 11-15 4-8 20
6 .02 575 12-16 10-14 3-7 <20
7 <.01 500 11-15 9-13 3-6 <20
3 .09 1290 17-24 15-21 8-14 30
4 .05 1000 16-22 14-20 7-13 25
5 .03 750 15-20 13-18 6-11 20
6 .02 645 14-18 12-16 5-9 20
7 .01 560 13-17 11-15 4-8 <20
3 .13 1430 19-26 17-23 10-16 35
4 .06 1110 18-25 16-22 9-15 30
5 .04 830 16-23 14-20 7-13 25
6 .03 715 14-20 12-18 6-11 20
7 .02 630 13-19 11-17 5-10 <20
4 .09 1330 19-27 17-24 10-16 30
5 .06 1000 18-26 16-23 8-15 25
6 .04 860 17-25 15-22 7-14 20
7 .03 750 16-23 14-20 6-12 20
8 .02 630 15-20 13-18 5-10 <20
5 .08 1170 20-30 18-27 10-19 30
6 .06 1000 19-28 17-25 9-17 25
7 .04 875 18-26 16-23 8-15 25
8 .03 740 16-24 14-21 6-13 20
9 .02 665 15-21 13-19 5-11 <20
6 .07 1150 21-32 19-29 10-20 25
7 .05 1000 20-30 18-27 9-18 25
8 .04 840 18-27 16-24 8-16 20
9 .03 760 17-26 15-23 6-14 <20
10 .02 695 16-25 14-22 5-13 <20
6 .09 1290 24-35 21-31 12-22 30
7 .07 1130 23-34 20-30 11-21 30
8 .05 950 20-31 18-28 9-19 25
9 .04 860 19-30 17-27 8-18 20
10 .03 780 18-29 16-26 7-17 <20
6 .11 1440 26-40 23-36 - 30
7 .08 1250 25-38 22-34 - 30
8 .06 1110 24-36 21-32 - 25
9 .05 955 22-33 20-30 - 25
10 .04 870 21-31 19-28 - 20
8 .10 1315 26-46 23-41 - 35
9 .07 1190 25-42 22-38 - 30
10 .06 1085 24-39 21-35 - 25
T
250
13
15
180
12
15
200
12
15
140
11
14
160
12
15
100
11
13
120
11
13
80
10
12
90
11
13
60
9
12
70
10
12
40
9
11
50
9
11
20
8
9
30
9
10
NC
Table 1 - Supply Air
CFM per
Foot
Number
of
Slots
Min. P
s
in H
2
O
Outlet
Velocity
(V
k
) FPM
Throw (T) in Feet
Minimum Ceiling
Height in Feet
Recommended Noise Criteria and Face Velocity Ranges are on page 75
Engineering Data
103
Engineering Data